Table 16 — Motor Limitations

STANDARD EFFICIENCY MOTORS

Nominal

Hp

Maximum

Bhp

Maximum Amps

Maximum

Watts

Motor

Efficiency

208

230

460

575

5

5.9

17.94

16.99

5,348

82.3

5.9

8.50

5.78

5,240

84.0

7.5

8.7

25.52

24.36

7,717

84.1

9.5

13.30

9.63

8,549

82.9

10

10.2

26.93

25.50

8,879

85.7

11.8

14.75

11.33

10,284

85.6

15

15.3

42.84

40.80

13,686

83.4

18.0

24.00

18.00

15,891

84.5

20

22.4

59.36

56.00

19,032

87.8

23.4

29.25

22.82

19,950

87.5

25

28.9

76.30

72.83

24,499

88.0

29.4

37.04

28.69

25,181

87.1

30

35.6

92.56

87.81

29,378

90.4

34.7

42.80

n/a

29,316

88.3

HIGH EFFICIENCY MOTORS

Nominal

Hp

Maximum

Bhp

Maximum Amps

Maximum

Watts

Motor

Efficiency

208

230

460

575

5

5.9

16.76

13.92

5,030

87.5

5.9

6.96

5,030

87.5

5.9

5.66

4,918

89.5

7.5

8.7

26.10

22.27

7,334

88.5

9.5

12.16

8,008

88.5

9.5

9.50

7,728

91.7

10

10.2

28.56

24.89

8,502

89.5

11.8

14.40

9,836

89.5

11.8

11.68

9,600

91.0

15

15.3

45.08

39.17

12,543

91.0

18.0

23.04

14,756

91.0

18.0

18.12

14,439

93.0

20

22.4

63.84

55.55

18,363

91.0

23.4

29.02

19,183

91.0

23.4

23.17

18,650

93.6

25

28.9

80.69

70.05

23,511

91.7

29.4

35.63

23,918

91.7

29.4

28.81

23,432

93.6

30

35.6

102.65

89.00

28,742

92.4

34.7

43.38

28,015

92.4

34.7

33.89

27,656

93.6

LEGEND

BHP — Brake Horsepower

NOTE: Extensive motor and electrical testing on the Carrier units has ensured
that the full horsepower range of the motor can be utilized with confidence.
Using your fan motors up to the horsepower ratings shown on the Motor Limi-
tations table will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected.

Table 17 — User Defined Set Points

SET POINT

FORMAT

DESCRIPTION

LIMITS

DEFAULT

OHSP

xx.xF

Occupied Heat Set Point

55 to 80 F

68

OCSP

xx.xF

Occupied Cool Set Point

55 to 80 F

78

UHSP

xx.xF

Unoccupied Heat Set Point

40 to 80 F

55

UCSP

xx.xF

Unoccupied Cool Set Point

75 to 95 F

90

SASP

xx.xF

Supply Air Set Point

45 to 70 F

55

OATL

xx.xF

Hi OAT Lockout Temperature

55 to 75 F

65

NTLO

xx.xF

Unoccupied OAT Lockout Temperature

40 to 70 F

50

RTIO

xx.x

Reset Ratio

0 to 10

3

LIMT

xx.x^F

Reset Limit

0 to 20 F

10

MDP

xxx%

Minimum Damper Position

0 to 100%

20

IAQS

xxxx

IAQ Set Point

1 to 5000

650

UHDB

xx.x^F

Unoccupied Heating Deadband

0 to 10

1

UCDB

xx.x^F

Unoccupied Cooling Deadband

0 to 10

1

LTMP

xx.xF

Low Temp. Min. Position

0 to 100

10

HTMP

xx.xF

High Temp. Min. Position

0 to 100

35

PES1

xx.xF

CV Power Exhaust Stage 1 Point

0 to 100

25

PES2

xx.xF

CV Power Exhaust Stage 2 Point

0 to 100

75

LEGEND

CV

Constant Volume

IAQ

Indoor Air Quality

OAT — Outdoor Air Temperature

39