Carrier 50EY User Manual

Page 36

Advertising
background image

Table 12 — Fan Performance, 50EJ/EK024-034 — Vertical Discharge Units

FOR EW/EY UNITS, REDUCE NET AVAILABLE EXTERNAL STATIC PRESSURE BY 0.3 IN. WG

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

4,000

322

0.77

401

1.09

466

1.43

523

1.78

575

2.13

622

2.50

666

2.87

707

3.25

5,000

361

1.14

433

1.50

494

1.86

548

2.23

598

2.62

643

3.00

686

3.40

726

3.80

6,000

403

1.62

468

2.01

526

2.41

577

2.81

624

3.21

668

3.62

709

4.04

748

4.46

7,000

448

2.22

508

2.65

561

3.08

609

3.50

654

3.93

696

4.37

736

4.81

773

5.25

8,000

495

2.97

549

3.42

599

3.88

645

4.33

687

4.79

727

5.25

765

5.71

801

6.18

8,250

507

3.18

560

3.64

609

4.10

654

4.56

696

5.02

735

5.49

773

5.96

809

6.43

9,000

543

3.85

593

4.34

639

4.82

682

5.30

723

5.78

761

6.27

797

6.76

832

7.24

10,000

592

4.90

638

5.41

682

5.91

722

6.42

760

6.93

797

7.44

832

7.95

865

8.46

11,000

642

6.10

685

6.64

725

7.17

764

7.70

800

8.24

835

8.77

868

9.30

900

9.84

12,000

693

7.48

733

8.04

771

8.60

807

9.15

841

9.71

874

10.26

906

10.82

937

11.38

12,500

718

8.23

757

8.80

794

9.37

829

9.94

862

10.51

895

11.08

926

11.64

956

12.21

13,000

744

9.03

781

9.62

817

10.20

851

10.78

884

11.36

915

11.93

946

12.51

975

13.09

13,750

783

10.32

818

10.92

852

11.52

885

12.12

917

12.71

947

13.31

977

13.90

1005

14.50

14,000

795

10.77

831

11.38

864

11.98

896

12.59

928

13.19

958

13.79

987

14.39

1015

14.99

15,000

847

12.71

880

13.34

912

13.96

943

14.59

972

15.21

1001

15.83

1029

16.45

1056

17.08

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.8

2.0

2.2

2.4

2.6

2.8

3.0

3.2

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

4,000

746

3.64

783

4.03

818

4.44

852

4.85

884

5.26

916

5.68

946

6.11

975

6.54

5,000

764

4.21

800

4.62

834

5.04

868

5.46

900

5.89

930

6.33

960

6.77

989

7.22

6,000

785

4.89

820

5.32

854

5.76

886

6.21

918

6.65

948

7.11

977

7.56

1006

8.02

7,000

809

5.70

843

6.16

876

6.61

908

7.08

939

7.54

968

8.01

997

8.49

1025

8.96

8,000

836

6.65

869

7.12

901

7.60

932

8.08

962

8.57

991

9.05

1019

9.55

1046

10.04

8,250

843

6.91

876

7.39

908

7.87

938

8.36

968

8.84

997

9.34

1025

9.83

1052

10.33

9,000

865

7.74

898

8.23

929

8.73

959

9.23

988

9.74

1016

10.24

1043

10.75

1070

11.27

10,000

897

8.98

928

9.49

958

10.01

987

10.53

1016

11.06

1043

11.58

1070

12.11

1096

12.64

11,000

931

10.37

961

10.91

990

11.45

1018

11.99

1046

12.54

1073

13.08

1099

13.63

1124

14.18

12,000

967

11.94

996

12.49

1024

13.06

1051

13.62

1078

14.18

1104

14.75

1129

15.31

1154

15.88

12,500

985

12.78

1014

13.35

1041

13.92

1068

14.49

1094

15.07

1120

15.64

1145

16.22

1169

16.80

13,000

1004

13.67

1032

14.25

1059

14.83

1086

15.42

1111

16.00

1137

16.59

1161

17.17

1185

17.76

13,750

1033

15.09

1060

15.69

1087

16.29

1112

16.88

1138

17.48

1162

18.08

1186

18.68

14,000

1043

15.59

1070

16.19

1096

16.79

1122

17.40

1147

18.00

1171

18.60

1195

19.21

15,000

1083

17.70

1109

18.32

1134

18.94

1159

19.56

1183

20.19

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

3.4

3.6

3.8

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

4,000

1004

6.97

1032

7.41

1059

7.86

5,000

1017

7.67

1045

8.12

1072

8.58

6,000

1034

8.49

1061

8.96

1087

9.43

7,000

1052

9.44

1079

9.93

1105

10.42

8,000

1073

10.54

1099

11.04

1125

11.55

8,250

1079

10.84

1105

11.34

1130

11.85

9,000

1096

11.78

1122

12.30

1147

12.82

10,000

1122

13.18

1147

13.71

1171

14.25

11,000

1149

14.73

1173

15.29

1197

15.84

12,000

1178

16.45

1202

17.03

12,500

1193

17.38

13,000

13,750

14,000

15,000

LEGEND

Bhp — Brake Horsepower

NOTES:
1. Fan performance is based on wet coils, economizer, roof curb,

cabinet losses, and clean 2-in. filters.

2. Conversion — Bhp to watts:

Bhp x 746

Watts =

Motor efficiency

3. VAV units will operate down to 70 cfm/ton.

36

Advertising