Carrier 50EY User Manual

Page 34

Advertising
background image

Table 10A — DIP Switch Configuration (Version 1.0 of Unit Control Software)

SETTING

1

2

3

4

5

6

7

8

OPEN

VAV

CCN/

Sensors

Expansion

I/O Board

Field
Test

ON

Modulated

Power

Exhaust

Time Guard Override

ON/ Set Min.

Damper Pos. ON

Gas Heat

Factory Test ON

CLOSED

CV

TSTAT

Base Board

Only

Field
Test

OFF

CV

Power

Exhaust

Time Guard Override

OFF/ Set Min.

Damper Pos. OFF

Electric Heat

Factory Test OFF

LEGEND

CCN

Carrier Comfort Network

CV

Constant Volume

I/O

Input/Output

POS.

Position

TSTAT — Thermostat
VAV

Variable Air Volume

NOTES:
1. The Factory Test DIP switch should not be enabled in the field.
2. The OPEN side of the DIP switch is marked ‘‘OPEN.’’ When the

rocker switch is on the ‘‘OPEN’’ side of the switch, the switch is
open.

3. If DIP switch no. 1 is open, DIP switch no. 2 is ignored, since VAV

units control to supply-air temperature.

Table 10B — DIP Switch Configuration (Version 2.0 of Unit Control Software)

SETTING

1

2

3

4

5

6

7

8

OPEN

VAV

VAV — Space Sensor

Installed

Expansion

Board

Field Test

ON

VAV —

Occupied

Heat

Enabled

Time Guard Override

ON

Gas Heat

Heat Pump

Operation

CV — CCN or Sensors

Used

CV —

Modulated

Power

Exhaust

IN CONJUNCTION
WITH FIELD TEST

— Set Minimum

Damper Position

CLOSED

CV

VAV — No Space Sensor

Base Control

Board Only

Field Test

OFF

VAV —

Occupied

Heat

Disabled

Time Guard Override

OFF

Electric Heat

Air Conditioner

Operation

CV — Thermostat

CV —

Constant

Volume

Power

Exhaust

LEGEND

CCN — Carrier Comfort Network
CV

Constant Volume

VAV

Variable Air Volume

NOTES:
1. The OPEN side of the DIP switch is marked ‘‘OPEN.’’ When the

rocker switch is on the ‘‘OPEN’’ side of the switch, the switch is
OPEN.

2. The configuration of DIP switches 2 and 5 are dependent on DIP

switch 1. If DIP switch 1 is set to OPEN (VAV operation), then DIP
switches 2 and 5 will configure CV functions.

3. When the unit is field-tested (DIP switch 4 to OPEN), the function

of DIP switch 6 changes and it is used to set the minimum damper
position.

Table 11A — DIP Switch Factory Settings (Version 1.0 of Unit Control Software)

UNIT

1

2

3

4

5

6

7

8

50EJ/EW

Closed

Closed

Closed

Closed

Closed

Closed

Closed

Closed

50EK/EY

Open

Closed

Closed

Closed

Open

Closed

Closed

Closed

Table 11B — DIP Switch Factory Settings (Version 2.0 of Unit Control Software)

UNIT

1

2

3

4

5

6

7

8

50EJ/EW

Closed

Closed

Closed

Closed

Closed

Closed

Closed

Closed

50EK/EY

Open

Closed

Closed

Closed

Closed

Closed

Closed

Closed

34