Table 3 — Electrical Data — 50EJ,EK,EW,EY024-048 (cont)

UNIT

SIZE

NOMINAL
VOLTAGE

(3 Ph 60 Hz)

VOLTAGE

RANGE

COMPRESSOR

OFM

IFM

POWER

EXHAUST

ELECTRIC

HEAT*

POWER SUPPLY

No. 1

No. 2

Min

Max

RLA

LRA

RLA

LRA

Qty

Hp

FLA (ea)

Hp

FLA

FLA

LRA

kW

FLA

MCA

MOCP†

048

208/230

187

254

82.1

446

69.2

345

4

1

5.3

20

59.4/

54.0

252.4/247.0

300/300

23.6

41.6

276.0/270.6

300/300

29/36

75.1/ 86.6

252.4/247.0

300/300

23.6

41.6

29/36

75.1/ 86.6

276.0/270.6

300/300

59/72

150.1/173.2

252.4/247.0

300/300

23.6

41.6

59/72

150.1/173.2

276.0/270.6

300/300

25

74.8/

68.0

267.8/261.0

300/300

23.6

41.6

291.4/284.6

300/300

29/36

75.1/ 86.6

267.8/261.0

300/300

23.6

41.6

29/36

75.1/ 86.6

291.4/284.6

300/300

59/72

150.1/173.2

267.8/261.0

300/300

23.6

41.6

59/72

150.1/173.2

291.4/284.6

300/300

30

88.0/

80.0

281.0/273.0

300/300

23.6

41.6

304.6/296.6

350/300

29/36

75.1/ 86.6

281.0/273.0

300/300

23.6

41.6

29/36

75.1/ 86.6

304.6/296.6

350/300

59/72

150.1/173.2

281.0/273.0

300/300

23.6

41.6

59/72

150.2/173.2

304.6/296.6

350/300

460

414

508

42.3

223

28.8

173

4

1

2.7

20

27

119.5

150

12.6

23.6

132.1

150

36

43.3

119.5

150

12.6

23.6

36

43.3

132.1

150

72

86.6

120.4

150

12.6

23.6

72

86.6

136.1

150

25

34

126.5

150

12.6

23.6

139.1

175

36

43.3

126.5

150

12.6

23.6

36

43.3

139.1

175

72

86.6

129.1

150

12.6

23.6

72

86.6

144.9

175

30

40

132.5

150

12.6

23.6

145.1

175

36

43.3

132.5

150

12.6

23.6

36

43.3

145.1

175

72

86.6

136.6

175

12.6

23.6

72

86.6

152.4

175

575

518

632

34.6

164

26.7

120

4

1

2.4

20

22

101.6

125

12.6

23.6

114.2

125

36

34.6

101.6

125

12.6

23.6

36

34.6

114.2

125

72

69.3

101.6

125

12.6

23.6

72

69.3

114.2

125

25

27

106.6

125

12.6

23.6

119.2

150

36

34.6

106.6

125

12.6

23.6

36

34.6

119.2

150

72

69.3

106.6

125

12.6

23.6

72

69.3

119.2

150

30

32

111.6

125

12.6

23.6

124.2

150

36

34.6

111.6

125

12.6

23.6

36

34.6

124.2

150

72

69.3

111.6

125

12.6

23.6

72

69.3

124.2

150

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v.

If power distribution voltage to unit varies from rated heater voltage, heater kW will
vary accordingly.

†Fuse or HACR circuit breaker.

NOTES:
1. In compliance with NEC requirements for multimotor and combination load equip-

ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit
breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than
2%. Use the following formula to determine the percent of voltage imbalance.

max voltage deviation from average voltage

% Voltage Imbalance = 100 x

average voltage

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage.

(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.

3. MCA calculation for units with electric heaters over 50 kW = (1.25 x IFM amps) +

(1.00 x heater FLA).