NOTES:
1. Weights include economizer (Std)

2.

Center of gravity.

3. Do not locate adjacent units with dis-

charge facing economizer inlet. Mini-
mum clearances to be:

Adjacent Units: 15

Ј

-0

Љ

Top of Units: No overhang
Condenser Coil: 4

Ј

-0

Љ

Economizer Side: 6

Ј

-0

Љ

Filter Access Side: 10

Ј

-0

Љ

(for re-

moval of evaporator coil)

4. For smaller service and operational

clearances, contact Carrier Applica-
tion Engineering department.

5. Bottom ducts designed to be attached

to accessory roof curb. If unit is mounted
on dunnage, it is recommended the
ducts be supported by cross braces as
done on accessory roof curb.

6. Dimensions are in inches. Dimen-

sions in [

] are in millimeters.

7. For units with electric heat, a field-

supplied 90° elbow must be installed
in the supply ductwork below the unit
discharge.

LEGEND

VFD — Variable Frequency Drive

UNIT SIZE

50EJ/EK

OPERATING

WEIGHT

(lb)

A

B

CORNER WEIGHT

(lb)

ft-in.

ft-in.

1

2

3

4

024

4016

5-11

3

8

3-5

11

16

823

914

1199

1080

028

4102

5- 8

1

2

3-7

5

8

844

859

1210

1189

030

4102

5- 8

1

2

3-7

5

8

844

859

1210

1189

034

4102

5- 8

1

2

3-7

5

8

844

859

1210

1189

Fig. 3 — Base Unit Dimensions, 50EJ/EK024-034