Carrier 50EY User Manual

Page 38

Advertising
background image

Table 14 — Fan Performance, 50EJ048 — Vertical Discharge Units

FOR EW UNITS, REDUCE NET AVAILABLE EXTERNAL STATIC PRESSURE BY 0.5 IN. WG

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

13,000

683

7.10

715

8.59

747

9.09

777

9.60

808

10.11

837

10.62

866

11.14

894

11.66

14,000

730

8.53

761

10.25

790

10.77

819

11.30

847

11.83

875

12.36

902

12.90

929

13.44

15,000

778

10.14

807

12.10

834

12.65

862

13.19

888

13.75

915

14.30

941

14.86

966

15.42

16,000

826

11.93

853

14.15

879

14.72

905

15.29

931

15.86

955

16.44

980

17.01

1004

17.59

17,000

875

13.90

900

16.42

925

17.01

949

17.60

973

18.19

997

18.78

1020

19.38

1043

19.98

18,000

923

16.06

947

18.90

971

19.51

994

20.12

1017

20.73

1039

21.34

1062

21.96

1084

22.58

19,000

972

18.42

995

21.61

1017

22.24

1039

22.87

1061

23.50

1083

24.13

1104

24.76

1125

25.40

20,000

1021

20.98

1042

24.55

1064

25.20

1085

25.85

1106

26.50

1126

27.15

1147

27.80

1167

28.46

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.8

2.0

2.2

2.4

2.6

2.8

3.0

3.2

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

13,000

921

12.18

948

12.71

975

13.24

1001

13.77

1026

14.30

1051

14.84

1076

15.39

1100

15.93

14,000

955

13.98

981

14.53

1006

15.08

1031

15.63

1056

16.18

1080

16.74

1103

17.30

1127

17.86

15,000

991

15.98

1015

16.54

1040

17.11

1063

17.68

1087

18.25

1110

18.83

1133

19.41

1155

19.99

16,000

1028

18.17

1051

18.76

1074

19.34

1097

19.93

1120

20.52

1142

21.12

1164

21.71

1185

22.31

17,000

1066

20.58

1089

21.18

1111

21.78

1133

22.39

1154

23.00

1175

23.61

1197

24.23

18,000

1106

23.19

1127

23.82

1148

24.44

1169

25.07

1190

25.69

19,000

1146

26.04

1166

26.68

1187

27.32

20,000

1187

29.11

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

3.4

3.6

3.6

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

13,000

1124

16.48

1148

17.03

1171

17.59

14,000

1150

18.43

1173

19.00

1195

19.57

15,000

1177

20.57

1199

21.16

16,000

17,000

18,000

19,000

20,000

LEGEND

Bhp — Brake Horsepower

NOTES:
1. Fan performance is based on wet coils, economizer, roof curb,

cabinet losses, and clean 2-in. filters.

2. Conversion − Bhp to watts:

Bhp x 746

Watts =

Motor efficiency

3. VAV units will operate down to 70 cfm/ton.

Table 15 — Air Quantity Limits

UNIT

50EJ,EK,EW,EY

MINIMUM HEATING

CFM

MINIMUM COOLING

CFM (VAV)

MINIMUM COOLING

CFM (CV)

MAXIMUM

CFM

024

6,000

2000

6,000

10,000

028

7,500

2500

7,500

12,500

030

8,250

2750

8,250

13,750

034

9,000

3000

9,000

15,000

038

10,500

3500

10,500

17,500

044

12,000

4000

12,000

20,000

048

13,500

4500

13,500

22,500

LEGEND

CV

Constant Volume

VAV — Variable Air Volume

38