PSEN op4F/H-s Series

29

You may use for example a safety relay of the PNOZsigma (PNOZ

s4, PNOZ s5) range as an evaluation device.

The wiring is described in the operating manual of the PNOZsigma

unit.

Do not use varistors, RC circuits or LEDs in parallel at relay inputs

or in series at OSSD outputs.


The OSSD1 and OSSD2 safety contacts cannot be connected in

series or in parallel, but can be used separately (Fig.17),

conforming to the plant’s safety requirements.


If one of these configurations is erroneously used, the device enters

into the output failure condition (see section 7 Diagnostic functions”).