Modbus, Communication, Gf-114 – AERCO Modbus Communications Manual User Manual

Page 17

Advertising
background image

Chapter 2

MODBUS

Communication

GF-114

Standard Register Assignments

USER MANUAL

OMM-0035_0C

05/18/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Page

17 of 200

2.2.2 C-More Boiler Controller Standard Holding Register Assignments

The Read/Write Input Register address assignments are listed in Table 2-2 which follows.

Unless otherwise specified, all Holding Register menu items are Read/Write (R/W)

Table 2-2: C-More Controller Standard Holding Register Address Mapping

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Comments

0 (0x0000)

Net Remote Set

Point

DEGREES_1 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions. R/W ONLY in

Remote Set Point Mode

1 (0x0001)

Net Direct Drive

% (0 to 100)

Normally Read Only. R/W

ONLY in Direct Drive Mode.

2 (0x0002)

Modbus Password int (0 to 65535)

Default = 0

3 (0x0003)

Password

int (0 to 65535)

Default = 0

4 (0x0004)

Internal Set Point

DEGREES_1 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions

Default = 130°F

5 (0x0005)

(Reserved)

6 (0x0006)

Time

Int (0 to 1439)

1count/min

7 (0x0007)

Date

int (0 to 65535)

1count/day

Date count starts with Jan.

1, 2000. For Example: Jan.

1 2001 would equal 365

counts

8 (0x0008)

Unit of Temp

bool (0, 1)

0= Degrees Fahrenheit (°F)

1=Degrees Celsius (°C)

Default = °F

9 (0x0009)

Baud Rate

enum (0, 1, 2, 3, 4)

0 = 2.4k

1 = 4.8k

2 = 9.6k

3 = 19.2k

For C-More RS232 port

ONLY

Default = 2 (9.6k)

10 (0x000A)

Unit Type

bool (0, 1)

0 = Boiler

1 = Water Heater

Default = Boiler

11 (0x000B)

Unit Size

enum (0, 1, 2, 3, 4, 5)

0 = 0.5 MBTU

1 = 1 MBTU

2 = 1.5 MBTU

3 = 2 MBTU

4 = 2.5 MBTU

5 = 3 MBTU

Default = 1 (1 MBTU)

Advertising