Chapter 1. introduction and general description, 1 introduction, 2 aerco bms and c-more controller models covered – AERCO Modbus Communications Manual User Manual

Page 7: Modbus, Communication, Gf-114

Advertising
background image

Chapter 1

MODBUS

Communication

GF-114

Introduction & Description

USER MANUAL

OMM-0035_0C

05/18/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Page

7 of 200

CHAPTER 1. INTRODUCTION AND GENERAL

DESCRIPTION

1.1 INTRODUCTION

The information contained in this manual provides general guidelines for implementing a

Modbus® communications network utilizing AERCO’s Boiler Management System (BMS) Model

168, Boiler Management System II (BMS II) Model 5R5-384, or AERCO Control System (ACS)

and C-More Boiler Controllers.
Throughout this document, the following terminology shall be used when referring to BMS

Model 168 and BMS II Model 5R5-384:

BMS: Applies to BMS Model 168 Only

BMS II:

Applies to BMS II Model 5R5-384 Only

BMS/BMS II: Applies to Both Models (BMS and BMS II)

BMS II/ACS: Applies to Both Models (BMS II and ACS)

ACS: Applies to ACS Only

All Modbus networks are implemented utilizing a Master-Slave technique where only one

device, the Master, can initiate a communication sequence. AERCO C-More Controllers can

only function as Slave devices in a Modbus network. However, the AERCO BMS can function

both as a Master controlling C-More Slaves, or as a Slave controlled by an Energy Management

System (EMS) or Building Automation System (BAS) developed by other manufacturers.

1.2 AERCO BMS AND C-MORE CONTROLLER MODELS COVERED

To easily determine if your AERCO BMS or C-More Boiler Controller is equipped with Modbus

capabilities, check the current software version as follows:

For BMS:

Apply power to the BMS

The BMS will display:

INITIALIZING followed by EPROM REV K

If

REV K or higher is displayed, the BMS Controller can support Modbus

If the REV level is lower than

K, the BMS Controller cannot support Modbus

For BMS II/ACS:

All BMS II Controllers support Modbus

For C-More:

Apply external power to the C-More Controller

Scroll through the Setup Menu and observe the displayed

Software Version

If

2.00 or higher is displayed, the C-More Controller can support Modbus

If a

Software Version lower than 2.00 is displayed, the C-More Controller cannot support

Modbus