Chapter 2

MODBUS

Communication

GF-114

Standard Register Assignments

USER MANUAL

OMM-0035_0C

05/18/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Page

31 of 200

Table 2-4: BMS/BMS II Standard Holding Register Address Mapping (Cont.)

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

52 (0x0034)

Offset On Time

Day 1 – Hours

00 to 23 Hours

Default = 0

53 (0x0035)

Offset On Time

Day 2 – Hours

00 to 23 Hours

Default = 0

54 (0x0036)

Offset On Time

Day 3 – Hours

00 to 23 Hours

Default = 0

55 (0x0037)

Offset On Time

Day 4 – Hours

00 to 23 Hours

Default = 0

56 (0x0038)

Offset On Time

Day 5 – Hours

00 to 23 Hours

Default = 0

57 (0x0039)

Offset On Time

Day 6 – Hours

00 to 23 Hours

Default = 0

58 (0x003A)

Offset On Time

Day 7 – Hours

00 to 23 Hours

Default = 0

59 (0x003B)

Offset Enable

0 or 1

0 = Disabled

1 = Enabled

Default = 0

(Disabled)

60 (0x003C)

Header Offset

0 to 5°F

Default = 0°F

61 (0x003D)

System Start Interlock 1, 2 or 3

1 = Either Intlk Opens Start

Relay

2 = Intlk1 Opens Start Relay

3 = Intlk 2 Open Start Relay

Default = 2

(Intlk 1)

62 (0x003E)

Thru

69 (0x0045)

(Reserved)

70 (0x0046)

Offset Off Time

Day 1 – Minutes

0 to 59 Minutes

Default = 0

71 (0x0047)

Offset Off Time

Day 2 – Minutes

0 to 59 Minutes

Default = 0

72 (0x0048)

Offset Off Time

Day 3– Minutes

0 to 59 Minutes

Default = 0

73 (0x0049)

Offset Off Time

Day 4– Minutes

0 to 59 Minutes

Default = 0

74 (0x004A)

Offset Off Time

Day 5 – Minutes

0 to 59 Minutes

Default = 0

75 (0x004B)

Offset Off Time

Day 6 – Minutes

0 to 59 Minutes

Default = 0