Appendix A

MODBUS

Communication

GF-114

Status Messages & Equations

USER MANUAL

OMM-0035_0C

05/18/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Page

91 of 200

Table A-2: C-More Status And Fault Messages - (Continued)

CODE

MESSAGE

DESCRIPTION

49

WAIT IGNITION RETRY

Second ignition trial after fault.

50

WAIT FAULT PURGE

Post purge after fault.

51

WAIT RETRY PAUSE

30 sec. pause before ignition retry.

52

EXHAUST TEMP SENSOR SHORT

Exhaust temperature sensor is shorted.

53

EXHAUST TEMP SENSOR OPEN

Exhaust temperature sensor is open.

54

WARNING EXHAUST TEMP HIGH

Exhaust temperature is close to alarm limit.

55

EXHAUST_TEMP_HIGH

Exhaust temperature has exceeded the alarm limit.

56

INLET WATER TEMP SENSOR SHORT

Inlet water temperature sensor is shorted.

57

INLET_WATER TEMP SENSOR OPEN

Inlet water temperature sensor is open.

58

WARNING IN WATER TEMP HIGH

Inlet water temperature is nearing the alarm limit.

59

WARNING IN WATER TEMP LOW

Inlet water nearing freezing temperature.

60

IINLET GAS PRESS SENSOR OPEN

Inlet gas pressure sensor connection input is open.

61

GAS PLATE DP SENSOR OPEN

Gas plate differential pressure sensor input is open.

62

INLET_WATER_FLOW_SENSOR_OPEN Inlet water flow sensor input is open.

63

WARNING IN WTR FLOW LOW

Inlet water flow is too low.

64

INLET_WATER HIGH_FLOW

Inlet water flow is too high.