Modbus, Communication, Gf-114 – AERCO Modbus Communications Manual User Manual

Page 39

Advertising
background image

Chapter 2

MODBUS

Communication

GF-114

Standard Register Assignments

USER MANUAL

OMM-0035_0C

05/18/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Page

39 of 200

Table 2-4: ACS Standard Input Register Address Mapping (Cont.)

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

55 (0x0037)

Boiler 31 Status

(Net Boiler 31)

119 = Not On-Line

120 = On-Line But Not

Fired

1–40 = Fired &

Sequence

121 = On-Line But

Disabled

122 = On-Line But

Faulted

56 (0x0038)

Boiler 32 Status

(Net Boiler 32)

Same As Above

57 (0x0039)

I/O Status

00 to 255

Bit map of Input/Output

Status:

Bit 0 = AUX Relay

Bit 1 = Fault Relay

Bit 2 = Sys Start Relay

Bit 3 = Empty

Bit 4 = Setback

Bt 5 = Interlock 2

Bit 6 = Interlock 1

Bit 7 = Empty

58 (0x003A)

Return Sensor Temp

40°F to 220°F

When Ret Sensor Mode

= Normal

59 (0x003B)

Net Blr 1 Outlet Temp

40°F to 220°F

When Blr Cntl Type = 1

or 2

60 (0x003C)

Net Blr 2 Outlet Temp

40°F to 220°F

61 (0x003D)

Net Blr 3 Outlet Temp

40°F to 220°F

62 (0x003E)

Net Blr 4 Outlet Temp

40°F to 220°F

63 (0x003F)

Net Blr 5 Outlet Temp

40°F to 220°F

64 (0x0040)

Net Blr 6 Outlet Temp

40°F to 220°F

65 (0x0041)

Net Blr 7 Outlet Temp

40°F to 220°F

66 (0x0042)

Net Blr 8 Outlet Temp

40°F to 220°F

67 (0x0043)

Net Blr 9 Outlet Temp

40°F to 220°F

68 (0x0044)

Net Blr 10 Outlet Temp 40°F to 220°F