Modbus, Communication, Gf-114 – AERCO Modbus Communications Manual User Manual

Page 45

Advertising
background image

Chapter 2

MODBUS

Communication

GF-114

Standard Register Assignments

USER MANUAL

OMM-0035_0C

05/18/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Page

45 of 200

Table 2-5: ACS Standard Holding Register Address Mapping (Cont.)

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

32 (0x0020)

Real Time Clock

Minutes

00 to 59

Present Time

33 (0x0021)

Real Time Clock

Hours

00 to 23 Hours

Present Time

34 (0x0022)

Real Time Clock

Day of Week

1 to 7

Present Day

35 (0x0023)

Real Time Clock

Year

00 to 99

Present Year

36 (0x0024)

Real Time Clock

Day of Month

01 to 31

Present Day of Month

37 (0x0025)

Real Time Clock

Month

01 to 12

Present Month

38 (0x0026)

Offset Temp Sun.

-50 to 50°F

Default = 0°F

39 (0x0027)

Offset Temp Mon.

-50 to 50°F

Default = 0°F

40 (0x0028)

Offset Temp Tue.

-50 to 50°F

Default = 0°F

41 (0x0029)

Offset Temp Wed.

-50 to 50°F

Default = 0°F

42 (0x002A)

Offset Temp Thu.

-50 to 50°F

Default = 0°F

43 (0x002B)

Offset Temp Fri.

-50 to 50°F

Default = 0°F

44 (0x002C)

Offset Temp Sat.

-50 to 50°F

Default = 0°F

45 (0x002D)

Offset On Time

Day 1 – Minutes

00 to 59 Minutes

Default = o

46 (0x002E)

Offset On Time

Day 2 – Minutes

00 to 59 Minutes

Default = 0

47 (0x002F)

Offset On Time

Day 3 – Minutes

00 to 59 Minutes

Default = 0

48 (0x0030)

Offset On Time

Day 4 – Minutes

00 to 59 Minutes

Default = 0

49 (0x0031)

Offset On Time

Day 5 – Minutes

00 to 59 Minutes

Default = 0

50 (0x0032)

Offset On Time

Day 6 – Minutes

00 to 59 Minutes

Default = 0

51 (0x0033)

Offset On Time

Day 7 – Minutes

00 to 59 Minutes

Default = 0

Advertising