Standard Register Assignments

Page

44 of 200 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph.: 800-526-0288 05/18/12

Table 2-5: ACS Standard Holding Register Address Mapping (Cont.)

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

18 (0x0012)

Derivative Gain

-2.00 to 2.00

(0.00 increments)

Default = 0.15

(Value x 100)

19 (0x0013)

Header Temp

Bandwidth

5 to 120°F

Default = 70°F

20 (0x0014)

Aux Relay Open

0 to 99%

Default = 45%

21 (0x0015)

Aux Relay Mode

0 or 1

0 = 100% Fire Rate

1 = 100% Fire Rate and Off

Default = 1

(100% Fire Rate & Off)

22 (0x0016)

Failsafe Mode

0 or 1

0 = Shutdown

1 = Constant Setpt

Default = 0

(Shutdown)

23 (0x0017)

Fault Alarm Relay

Mode

0, 1, 2, 3

0 = All Faults,

1 = No Interlock

2 = Interlock 1

3 = Interlock 2

Default = 0

(All Faults)

24 (0x0018)

Fault Alarm Clear

Method

0 or 1

0 = Automatic

1 = Manual

Default = 0

(Automatic)

25 (0x0019)

Boiler Operation

Mode

0, 1 or 2

0 = Parallel

1 = Sequential

2 = Combination

Default = 1

(Sequential)

26 (0x001A)

Not Applicable

27 (0x001B)

(Reserved)

28 (0x001C)

(Reserved)

29 (0x001D)

(Reserved)

30 (0x001E)

Max Power Input

50 to 100%

Default = 100%

(Fire Rate)

31 (0x001F)

Sys Intlk Config

0 or 1

0 = Always Enabled

1 = Start Enabled

Default = 1

(Start Enabled)