Table 2-5: ACS Standard Holding Register Address Mapping (Cont.)

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

131 (0x0083)

Outside Temp Sensor Offset -50 to +50°F

Default = 0

132 (0x0084)

Dyn Up

0 to 300%/Min

Default = 20

133 (0x0085)

Dyn Down

0 to 300%/Min

Default = 200

134 (0x0086)

Fault Alarm Boilers

0 = No Blr Faults

1 = All Blr Faults

Default = 0

135 (0x0087)

4 to 20 mA Current Offset

-1.00 mA to 1.00 mA

Default = 0

136 (0x0088)

Return Sensor Offset

-10.0°F to 10.0°F

Default = 0

137 (0x0089)

Load Start Pct

1 to Blr Start Level

Default = 1

138 (0x008A)

Load Stop Pct

0 to Load Start Pct - 1

Default = 0

139 (0x008B)

PASS THROUGH WRITE

ENABLE

0 = Disabled

1 = Enabled

Default = 0

140 (0x008C)

LEAD BOILER SELECT

0 (None) or 1

Default = 0

141 (0x008D)

LAST BOILER SELECT

0 (None) or 1 - 32

Default = 0

142 (0x008E)

ROTATE TIME

0 to 999 hrs

?Default = 168 hrs

143 (0x008F)

NUMBER OF DHW

BOILERS

0 to 8

Default = 0

144 (0x0090)

DHW OPTION

0 to 3

0 = No Option

1 = Option 1 (1 Valve)

2 = Option 2 (2 Valve)

3 = Option 3 (Boost)

Default = 0

145 (0x0091)

SYSTEM RELAY OPTION

0 or 1

0 = Normal

1 = DHW Valve 1 Close

Default = 0

146 (0x0092)

NUMBER DHW PRIORITY O to Num DHW Boilers - 1 Default = 1

147 (0x0093)

DHW SIGNAL

0 or 1

0 = No Signal

1 = Special Signal

Default = 0

168 (0x0094)

RETURN SENSOR MODE

0 to 2

0 = Off

1 = Normal (Return Sensor)

2 = DHW/Tank Temp

Default = 0

149 (0x0095)

HIGH DB SETPT ENABLE

LEVEL

Blr Stop Level to 100%

Default = Blr Stop

Level