Modbus, Communication, Gf-114 – AERCO Modbus Communications Manual User Manual

Page 18

Advertising
background image

GF-114

MODBUS

Communication

Chapter 2

OMM-0035_0C

USER MANUAL

Standard Register Assignments

Page

18 of 200 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph.: 800-526-0288 05/18/12

Table 2-2: C-More Controller Standard Holding Register Address Mapping

(Continued)

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Comments

12 (0x000C)

Boiler Mode

enum (0, 1, 2, 3, 4):

0 = Constant Setpt

1 = Remote Setpt

2 = Direct Drive

3 = Combo Unit

4 = Outdoor Reset

Default = 0

(Constant Setpt)

13 (0x000D)

Remote Signal

enum (0, 1, 2, 3):

0 = 4 - 20 mA /1 - 5V

1 = 0 -20mA/0 - 5V

2 = PWM Input

3 = Network

Default = 0

(4 - 20 mA/1 - 5V)

14 (0x000E)

Bldg Ref Temp

DEGREES_1 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions

15 (0x000F)

Reset Ratio

Int (1 to 99 counts)

Actual Range = 0.1 to 9.9

(Counts = Actual x 10)

Actual Default = 1.2

Therefore:

1.2 x 10 = 12 counts

16 (0x0010)

Outdoor Sensor

Enable

bool (0,1)

0 = False

1 = True

Default = 0 (False)

17 (0x0011)

System Start Temp DEGREES_2 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions

Default = 60°F

18 (0x0012)

Set Point Lo Limit

DEGREES_1 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions

Default = 60°F

19 (0x0013)

Set Point Hi Limit

DEGREES_1 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions

Default = 200°F

20 (0x0014)

Temp Hi Limit

DEGREES_1 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions

Default = 210°F

21 (0x0015)

Max Fire Rate

% (40 - 100)

Default = 100%

22 (0x0016)

Pump Delay Timer MIN_UNITS (0 to 30)

1count/min

Default = 0 min.

23 (0x0017)

Aux Start On Delay SEC_UNITS (0 to 120)

1count/sec

Default = 0 sec.