APPENDIX A: BOILER MENU DESCRIPTIONS

Page 136 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0097_0D

Ph.: 800-526-0288

GF-142

APPENDIX A: BOILER MENU ITEM DESCRIPTIONS – Continued

MENU LEVEL & OPTION

DESCRIPTION

TUNING MENU

Prop Band

Generates a fire rate based on the error that exists
between the setpoint temperature and the actual outlet
temperature. If the actual error is less than the
proportional band setting (1 to 120°F), the fire rate will be
less than 100%. If the error is equal to or greater than
the proportional band setting, the fire rate will be 100%.

Integral Gain

This sets the fraction of the output, due to setpoint error,
to add or subtract from the output each minute to move
towards the setpoint. Gain is adjustable from 0.00 to
1.00 (Default is 1.0).

Derivative Time

This value (0.0 to 2.0 min.) responds to the rate of
change of the setpoint error. This is the time that this
action advances the output.

WARMUP

The feature embodied in the next three menu items
eliminates Temperature Overshoots during the “Warmup”
period of a cold ignition cycle on all boilers by temporarily
modifying the PID Gain parameter during warmup and
for a period defined in the Tuning Menu.

Warmup Prop Band

Range = 1-120

Default = 95

Warmup Int Gain

Range = 1-200

Default = 50

Warmup PID Timer

Range = 1-240

Default = 20

Reset Defaults?

Allows Tuning Menu options to be reset to their Factory
Default values.