APPENDIX E – RECOMMENDED PERIODIC TESTING

OMM-0097_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 145 of 188

GF-142

Ph.: 800-526-0288

Appendix E: RECOMMENDED PERIODIC TESTING

WARNING

Periodic testing of all boiler controls and safety devices is required to determine that they are
operating as designed. Precautions shall be taken while tests are being performed to protect
against bodily injury and property damage. The owner or user of an automatic boiler system
should set up a formal system of periodic preventive maintenance and testing. Tests should be
conducted on a regular basis and the results recorded in a log-book.

Item

Frequency

Accomplished

By

Remarks

Refer to indicated sections of this manual for detailed procedures

Gauges, monitors and
indicators

Daily

Operator

Visual inspection and record readings in operator log

Instrument and
equipment settings

Daily

Operator

Visual check against factory recommended
specifications

Weekly

Operator

Verify factory settings

Firing Rate Control

Semi-Annually Service Technician Verify factory settings

Annually

Service Technician

Check with combustion calibration test equipment.
See sections 4.3 and 7.4.

Flue, vent, stack or
intake air duct

Monthly

Operator

Visually inspection condition and check for
obstructions

Spark Igniter-Injector

Weekly

Operator

See section 7.2

Air/Fuel Valve position

Weekly

Operator

Check position indicator dial (section 3.11)

SSOV Leakage test

Annually

Service Technician

Check for leakage in accordance with the SSOV
manufacturer’s (Siemens) recommendations.

Flame failure

Weekly

Operator

Close manual gas shutoff valve and check safety
shutdown. See section 6.7

Flame signal strength

Weekly

Operator

Check flame strength using the Control Panel
Operating Menu. See section 3.4.

Low water level cut off
and alarm

Weekly

Operator

See section 6.4

Slow drain test

Semi-Annually

Operator

Perform a slow drain test in accordance with ASME
Boiler and Pressure Vessel Code,
Section IV.

High water temperature
safety control test

Annually

Service Technician See section 6.5

Operating controls

Annually

Operator

See section 3.2

Low air flow

Monthly

Operator

See section 6.8

High and low gas
pressure interlocks

Monthly

Operator

See sections 6.2 and 6.3

Air/Fuel Valve purge
position switch

Annually

Service Technician See section 6.10

Air/Fuel Valve ignition
position switch

Annually

Service Technician See section 6.11

Safety valves

As required

Operator

Check per A.S.M.E. Boiler and Pressure Vessel
Code, Section IV

Inspect burner
components

Semi-Annually Service Technician

See section 7.6

Condensate Trap

Semi-

Annually

Operator

See section 7.7

Oxygen (O

2

) Level

Monthly

Operator

Verify oxygen level is between 3% and 8% during
boiler operation