10 purge switch open during purge – AERCO BMK 1500-2000 User Manual

Page 82

Advertising
background image

Benchmark 1500 - 2000 Boilers

CHAPTER 6 – SAFETY DEVICE TESTING

Page 82 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0097_0D

Ph.: 800-526-0288

GF-142

Figure 6-5: SSOV Actuator Cover Location

6.10 PURGE SWITCH OPEN DURING PURGE

The Purge Switch (and Ignition Switch) is located on the Air/Fuel Valve. To check the switch,
proceed as follows:

Purge Switch Open During Purge

1. Set the unit’s ON/OFF switch to the OFF position. Place the unit in manual mode and

set the valve position between 25% and 30%.

2. Remove the Air/Fuel Valve cover by rotating the cover counterclockwise to unlock it

(see Figure 6-6).

3. Remove one of the two wires (#171 or #172) from the Purge Switch (Figure 6-6).

4. Initiate a unit start sequence.

5. The unit should begin its start sequence, then shut down and display PRG SWITCH

OPEN DURING PURGE.

6. Replace the wire on the Purge Switch and depress the CLEAR button. The unit should

restart.

SSOV

ACTUATOR

COVER

ACTUATOR
COVER
SCREW

Advertising