Benchmark 1500 - 2000 Boilers

CHAPTER 6 – SAFETY DEVICE TESTING

OMM-0097_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 75 of 188

GF-142

Ph.: 800-526-0288

6.5 WATER TEMPERATURE FAULT TEST

A high water temperature fault is simulated by adjusting the automatic over-temperature switch.
This switch is accessible from the front of the unit as shown in Figure 6-2.

Water Temperature Fault Test

1. Start the unit in the normal operating mode. Allow the unit to stabilize at its setpoint.

2. Lower the adjustable over-temperature switch setting to match the displayed OUTLET

TEMPERATURE.

3. Once the adjustable over-temperature switch setting is approximately at, or just below,

the actual outlet water temperature, the unit should shut down. The FAULT indicator
should start flashing and a HIGH WATER TEMP SWITCH OPEN fault message should
be displayed. It should not be possible to restart the unit.

4. Reset the adjustable over-temperature switch to its original setting.

5. The unit should start once the adjustable temperature limit switch setting is above the

actual outlet water temperature.

6. Once the adjustable over-temperature switch setting is approximately at, or just below,

the actual outlet water temperature, the unit should shut down. The FAULT indicator
should start flashing and a HIGH WATER TEMP SWITCH OPEN fault message should
be displayed. It should not be possible to restart the unit.

7. Reset the adjustable over-temperature switch to its original setting.

8. The unit should start once the adjustable temperature limit switch setting is above the

actual outlet water temperature.






















Figure 6-2: Temperature Limit Switch Location

ADJUSTABLE
TEMPERATURE
LIMIT SWITCH

MANUAL
SWITCH
RESET
BUTTON

OVER
TEMPERATURE
LIMIT DIGITAL
CONTROLLER

MANUAL
TEMPERATURE
LIMIT SWITCH