Benchmark 1500 - 2000 Boilers

CHAPTER 6 – SAFETY DEVICE TESTING

Page 72 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0097_0D

Ph.: 800-526-0288

GF-142

6.2 LOW GAS PRESSURE FAULT TEST

To simulate a low gas pressure fault, refer to Figure 6-1a and perform the following steps:

Figure 6-1a:

BMK 1500/2000: Low Gas Pressure Test

Low Gas Pressure Fault Test

1. Close the leak detection ball valve located at the low gas pressure switch (see Figure 6-

1a).

2. Remove the 1/4“ plug from the ball valve at the low gas pressure switch shown in the

lower portion of Figure 6-1a.

3. Install a 0 – 16“ W.C. manometer or a W.C. gauge where the 1/4" plug was removed.

4. Slowly open the ball valve near the low gas pressure switch.

5. Place the unit in Manual Mode and adjust the Air/Fuel Valve position (% open) between

25 and 30%.

6. While the unit is firing, slowly close the external manual gas shut-off valve.

7. The unit should shut down and display a GAS PRESSURE fault message at

approximately: 3.6” W.C. for both BMK 1500 and BMK 2000.

8. Fully open the external manual gas shut-off valve and press the CLEAR button on the

Control Box.

9. The fault message should clear and the FAULT indicator should go off. The unit should

restart.

10. Upon test completion, close the ball valve and remove the manometer. Replace the 1/4“

plug removed in step 1.

NATURAL
GAS INLET

SSOV

HIGH GAS

PRESSURE

SWITCH

LOW GAS
PRESSURE
SWITCH

MANUAL
SHUT-OFF
VALVE

1/4” NPT PLUG
And Ball Valve (install
manometer here for LOW
GAS PRESSURE FAULT
TEST

LOW GAS BALL VALVE