AERCO BMK 1500-2000 User Manual

Page 56

Advertising
background image

Benchmark 1500 - 2000 Boilers

CHAPTER 4 – INITIAL START-UP

Page 56 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0097_0D

Ph.: 800-526-0288

GF-142

BMK 1500 Natural Gas Combustion Calibration (Cont.)

25. The oxygen level at the 80% valve position should be as shown below. Also, ensure that

the nitrogen oxide (NOx) and carbon monoxide (CO) readings do not exceed the
following values:

Combustion Calibration Readings – 80% valve Position

Valve Position

Oxygen (O

2

) %

Nitrogen Oxide (NOx)

Carbon Monoxide (CO)

80%

5.9% ± 0.5%

≤20 ppm

<100 ppm

26.

If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output voltage to the blower motor as indicated on the

display. Pressing the ▲ arrow key increases the oxygen level and pressing the down ▼
arrow key decreases the oxygen level.

27. Once the oxygen level is within the specified range at 80%, press the ENTER key to

store the selected blower output voltage for the 80% valve position. Record all readings
on the Combustion Calibration Sheets provided.

28. Repeat steps 20 through 27 for valve positions of 60%, 45%, 30% and 16%. The oxygen

(O

2

), nitrogen oxide (NOx) and carbon monoxide (CO) should remain within the same

limits for all valve positions as shown in the following table.

NOTE

If NOx readings exceed the target values shown (<20 ppm),
increase the O

2

level up to 1% higher than the listed calibration

range shown in the table. Record the increased O

2

value on the

Combustion Calibration sheet.

Combustion Calibration Readings

Valve Position

Oxygen (O

2

) %

Nitrogen Oxide (NOx)

Carbon Monoxide (CO)

60%

6.0% ± 0.5

<20 ppm

<100 ppm

45%

6.3% ± 0.5

<20 ppm

<100 ppm

30%

6.3% ± 0.5

<20 ppm

<100 ppm

16%

6.0% ± 0.5

<20 ppm

<100 ppm

29. If the oxygen level at the 16% valve position is too high and the Blower voltage is at the

minimum value, you can adjust the idle screw (TAC valve) which is recessed in the top of
the Air/Fuel Valve (see Figure 4-4). Rotate the screw 1/2 turn clockwise (CW) to add fuel
and reduce the O

2

to the specified level. Recalibration MUST be performed again from

60% down to 16% after making a change to the idle screw (TAC valve).

30. This completes the BMK 1500 Natural Gas combustion calibration procedures.

Advertising