Benchmark 1500 - 2000 Boilers

CHAPTER 3 – OPERATION

Page 50 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0097_0D

Ph.: 800-526-0288

GF-142

3.11 START/STOP LEVELS

The start and stop levels are the Air/Fuel Valve positions (% open) that start and stop the unit,
based on load. These levels are Factory preset as follows:

BMK 1500

BMK 2000

Start Level:

24%

24%

Stop Level:

16%

16%

Normally, these settings should not require adjustment.

Note that the energy input of the boiler is not linearly related to the Air/Fuel Valve position. Refer
to Table 3-8 for the relationship between the energy input and Air/Fuel Valve position for a BMK
1500 MBH boiler running on natural gas.

Table 3-8a:

BMK 1500:

Relationship Between Air/Fuel Valve Position and

Energy Input Running On Natural Gas

Air/Fuel Valve

Position

(% Open)

Energy Input

(BTU/Hr)

Boiler Energy Input
(% of Full Capacity)

16% (Stop Level)

76,000

5.0%

20%

127,000

8.5%

30%

366,000

24.4%

40%

629,000

41.9%

50%

822,000

54.7%

60%

977,000

65.0%

70%

1,119,000

74.5%

80%

1,255,000

83.5%

90%

1,396,000

92.9%

100%

1,502,000

100%

Table 3-8b:

BMK 2000:

Relationship Between Air/Fuel Valve Position and

Energy Input Running On Natural Gas

Air/Fuel Valve

Position

(% Open)

Energy Input

(BTU/Hr)

Boiler Energy Input
(% of Full Capacity)

16% (Stop Level)

100,000

6.7%

20%

143,000

11%

30%

388,000

23%

40%

759,000

37%

50%

1,069,000

51%

60%

1,283,000

61%

70%

1,476,000

74%

80%

1,675,000

83%

90%

1,833,000

93%

100%

2,000,000

100%