CHAPTER 2 – INSTALLATION

Page 32 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0097_0D

Ph.: 800-526-0288

GF-142

1.

Install the sequencing valve in the boiler’s hot water outlet pipe.

Figure 2-13: Sequencing Valve Installed

2.

The boiler’s shell harness has one unused cable. One end of this cable is connected to
the DELAYED INTERLOCK IN terminals in the I/O board (see Figure 2-14) while the other
end contains a Molex connector with a jumper wire inserted in it (this jumper wire allows
units that do not have a sequencing valve to operate normally). Find the free end of this
cable inside the unit’s enclosure.

Figure 2-14: Sequencing Valve Installed

3.

Remove the jumper wire from the Molex connector and then plug it into the sequencing
valve’s connector.

HOT WATER

OUTLET

SEQUENCING

VALVE