APPENDIX G

G-1

CONNECT

5/

8''

I.D

. HOSE TO CONDENSATE DRAIN

SHELL DRAIN VALVE

*

RELIEF VALVE

*

(NOTE

5)

6''

LINE SIZE BYPASS

PRESSURE REDUCING FILL VALVE

BACKFLOW PREVENTER

EXPANSION TANK

DIAPHRAGM TYPE

COLD WATER IN

MAKE

-UP

, ELIMINATION AND

TYPICAL LOCATION OF

SYSTEM PUMP

SEPARATOR

AIR

AIR VENT

BOILER WATER IN

BOILER WATER OUT

MANDATORY GAS PRESSURE REGULATOR

(SUPPLIED BY OTHERS

)

7.

7"

W

.C

. (

PROPANE GAS

) AT MAXIMUM BTU

/H INPUT

GAS IN

- SEE GF

-1030

FOR GAS PIPING INSTALLATION

MAINTAIN A REGULATED

8.

8''

W

.C

. PRESSURE

(NATURAL GAS

)/

1-

1/

4''

MANUAL SHUTOFF

*

DIRT TRAP

2'

EXPANSION COMPONENTS

AUTOMATIC

DRAIN

CHECK VALVE

LEGEND

STOP VALVE

Y-

STRAINER

UNION

GAS FIRED BOILER

KC

1000 1

MIL

. BTU LOW NOx

SINGLE UNIT INSTALLATION

NORTHVALE

, NJ

07647

INTERNATIONAL

, INC

.

APPD

.

DWN

.BY

SCALE

DATE

CZ

012207

DATE

JK

NTS

012207

AERCO

SD

-A

-711

C

REV

.

(FOR DUAL

-FUEL INSTALLATION

, SEE NOTE

7)

(FOR DUAL

-FUEL INSTALLATION

, SEE NOTE

7)

3)

FOR ACTUAL SIZES AND LOCATIONS OF PIPING AND OTHER CONNECTIONS TO THE BOILER

,

OF

6''

FROM BOILER FITTINGS TO PREVENT INTERFERENCE WITH REMOVAL OF BOILER

FREELY

, BY GRAVITY

, TO A CONVIENIENT FLOOR DRAIN

. RELIEF VALVE SHOULD BE PIPED

6)

SEE PRODUCT SPECIFICATION FOR PRESSURE DROPS AT VARIOUS FLOWS

.

4)

SHELL DRAIN VALVE AND CONDENSATE HOSE SHOULD BE ARRANGED TO PERMIT THE FLUIDS TO DRAIN

5)

LOCATE WATER INLET AND OUTLET FITTINGS

(i.

e.

UNIONS

, ELBOWS

, ETC

.)

AND ALL PIPING A MINIMUM

PANELS AND COVERS

.

LOCATE GAS PRESSURE REGULATOR A MINIMUM OF

2'

FROM BOILER

.

SEE DIMENSIONAL DRAWING

.

VERTICALLY TO A HEIGHT

18

'' ABOVE FLOOR

.

1)

THIS IS A TYPICAL INSTALLATION DRAWING

.

LOCAL CODES AND AUTHORITIES SHOULD BE CONSULTED

.

2)

ALL

(*)

ITEMS ARE INCLUDED SEPARATELY IN SHIPMENT

.

NOTES

:

7)

FOR DUAL

-FUEL INSTALLATION

:

- INSTALL APPROPRIATE REGULATOR FOR CURRENT FUEL IN USE

.

- INSTALLER MUST CHECK WITH LOCAL CODES REGARDING ACCEPTABLE METHOD OF DESIGNING DUAL

GAS PIPING SYSTEM TO PREVENT DIRECT FLOW OF FUEL FROM ONE SYSTEM OF GAS PIPING INTO

ANOTHER

(FOR EXAMPLE

, FROM NATURAL GAS TO PROPANE

, AND VICE VERSA

).