Section 5 - mode of operation, 1 introduction, 2 indoor/outdoor reset mode – AERCO KC1000 Low NOx Boiler July 2011 User Manual

Page 43: 1 reset ratio, Building reference temperature, 3 outdoor air temperature sensor installation, 4 indoor/outdoor startup, Mode of operation

Advertising
background image

MODE OF OPERATION

5-1

SECTION 5 - MODE OF OPERATION

5.1 INTRODUCTION

The following paragraphs provide detailed

descriptions of the six different modes of

operation for the KC1000 Boiler. Each unit is

shipped from the factory tested and configured

for the ordered mode of operation. All

temperature related parameters are at factory

defaults and work well in most applications.

However, it may be necessary to change certain

parameters to customize the unit to the system.

A complete listing and descriptions of the

temperature related parameters are included in

Appendix A. Factory defaults are listed in

Appendix E. After reading this section,

parameters can be customized to suit the needs

of the specific application.

5.2 INDOOR/OUTDOOR RESET MODE

This mode of operation is based on outside air

temperatures. As the outside air temperature

decreases, the supply header temperature will

increase and vice versa. For this mode, it is

necessary to install an outside air sensor as well

as select a building reference temperature and a

reset ratio.

5.2.1 RESET RATIO

Reset ratio is an adjustable number from 0.1 to

9.9. Once it is adjusted, the supply header

temperature will increase by that number for

each degree that the outside air temperature

decreases. For instance, if a reset ratio of 1.6 is

used, for each degree that outside air

temperature decreases the supply header

temperature will increase by 1.6 degrees.

5.2.2. BUILDING REFERENCE

TEMPERATURE

This is a temperature from 40°F to 240°F. Once

selected, it is the temperature that the system

references to begin increasing its temperature.

For instance, if a reset ratio of 1.6 is used and

we select a building reference temperature of

70°F, then at an outside temperature of 69°F,

the supply header temperature will increase by

1.6° to 71.6°F.

5.2.3 OUTDOOR AIR TEMPERATURE

SENSOR INSTALLATION

The outdoor air temperature sensor must be

mounted on the North side of the building in an

area where the average outside air temperature

is expected. The sensor must be shielded from

the sun's direct rays, as well as from direct

impingement by the elements. If a cover or

shield is used, it must allow free air circulation.

The sensor may be mounted up to 200 feet from

the unit. Sensor connections are made inside

the Input/Output (I/O) Box on the left side of the

KC1000 Boiler. Connections are made at the

terminals labeled OUTDOOR SENSOR IN and

SENSOR COMMON inside the I/O Box using

shielded 18 to 22 AWG wire. A wiring diagram

is provided on the cover of the I/O Box. Refer to

Section 2, paragraph 2.6.2 for additional wiring

information.

5.2.4 INDOOR/OUTDOOR STARTUP

1. Refer to the indoor/outdoor reset ratio charts

in Appendix D.

2. Choose the chart corresponding to the

desired building reference temperature.

3. Go down the left column of the chart to the

coldest design outdoor air temperature

expected in your area.

NOTE:

A design engineer typically provides design

outdoor air temperature and supply

header

temperature data

4. Once the design outdoor air temperature is

chosen, go across the chart to the desired

supply header temperature for the design

temperature chosen in step 3.

5. Next, go up that column to the Reset Ratio

row to find the corresponding reset ratio.

6. Access the Configuration Menu and scroll

through it until the display shows Bldg Ref

Temp (Building Reference Temperature).

7. Press the

CHANGE key. The display will

begin to flash.

8. Use the

and arrow keys to select the

desired building reference temperature.

9. Press

ENTER to save any changes.

10. Next, scroll through the Configuration Menu

until the display shows Reset Ratio.

Advertising