Figure 2.12, Sealed combustion air connection, Installation – AERCO KC1000 Low NOx Boiler July 2011 User Manual

Page 21

Advertising
background image

INSTALLATION

2-11

from a clean area outdoors for the protection

and longevity of the equipment.

The more common methods of supplying

combustion air are outlined below. For more

information on combustion air, consult the

AERCO GF-1050, Venting and Combustion Air

Guide.

2.10.1 COMBUSTION AIR FROM

OUTSIDE THE BUILDING

Air supplied from outside the building must be

provided through two permanent openings. For

each unit these two openings must have a free

area of not less than one square inch for each

4000 BTUs input of the equipment or 250

square inches of free area. The free area must

take into account restrictions such as louvers

and bird screens. For Canada installations,

refer to the requirements specified in CSA

B149.1-10, 8.4.1 and 8.4.3.

2.10.2 COMBUSTION AIR FROM INSIDE

THE BUILDING

When combustion air is provided from within the

building, it must be supplied through two

permanent openings in an interior wall. Each

opening must have a free area of not less than

one square inch per 1000 BTUH of total input or

1000 square inches of free area. The free area

must take into account any restrictions such as

louvers.

NOTE

KC1000 units equipped with Low NOx

Burners require an optional Cold Air

Damper for operation with Direct Vent/

Sealed Combustion. The Cold Air Damper

is also required when the unit is installed

in an area where the combustion air

supply temperature can drop below 55°F.

Refer to the following paragraph (2.10.3)

and GF-1050 for installation details.

2.10.3 SEALED COMBUSTION

The KC Boiler is UL approved for 100% sealed

combustion application when installed properly.

When a sealed combustion air application is

installed, the sealed combustion air piping must

be deducted from the maximum allowable

discharge piping amounts. Each unit must have

a minimum 6" diameter connection made to the

special Inlet Air Adapter # GP-18917 available

from AERCO. This adapter bolts directly on to

the air inlet of the unit’s blower. See installation

instructions with adapter. All inlet air ducts must

be sealed air tight.

In addition, Cold Air Damper # 99026 must be

installed. It should be located along the inlet duct

run as close as possible to the KC1000 (See

Figure 2.12). The Cold Air Damper must be

placed on individual sections (one Damper per

unit), not in a manifold section. The adjustment

screw on the Damper should be moved to the

center of the slot position and tightened 1/2 turn

past “finger-tight”. DO NOT over-tighten.

See AERCO Venting Guide GF-1050 for further

details.

6" MINIMUM

6x3 REDUCER

COLD AIR DAMPER
(FOR KC1000 LOW NOX)

Figure 2.12

Sealed Combustion Air Connection

2.10.4 TEMPORARY COMBUSTION AIR

FILTERING DURING CONSTRUCTION

When the AERCO KC1000 Boiler is used to

provide heat temporarily during ongoing building

construction, drywall dust, sawdust and similar

particles can accumulate in the unit’s

combustion air intake filter and block combustion

air flow. In these situations, AERCO recom-

mends that a disposable air intake filter be

installed, temporarily, above the boiler

combustion air inlet.

AERCO recommends that the temporary air filter

be cut from a McMaster-Carr part no. 2122K315

Polyester Air Filter Roll Tackfield, ½” thick, 16”

wide, or equivalent. Cover the KC1000 air inlet

with the blue side of the filter material facing

outward to hold the dust on the outside surface.

Maximize the surface area of the filter covering

the 8" diameter opening by creating a dome out

of the filter material.
During construction check the filter for dust

accumulation and replace it when the

accumulation becomes noticeable.

Advertising