2.6.1 CONSTANT SETPOINT MODE

The Constant Setpoint Mode is used when it is

desired to have a fixed setpoint that does not

deviate. No wiring connections other than

electrical supply connections are required for

this mode. However, if desired, fault monitoring

or enable/disable interlock wiring can be utilized

(see paragraphs 2.7.9 and 2.7.10).

2.6.2 INDOOR/OUTDOOR RESET MODE

This mode of operation increases supply water

temperature as outdoor temperatures decrease.

An outside air temperature sensor (AERCO PN

122790) is required. The sensor MUST BE

wired to the I/O Box wiring terminals (see Fig.

2.11). For more information concerning the

outside air sensor installation, refer to paragraph

2.7.1. For programming and setup instructions

concerning the indoor/outdoor-reset mode of

operation, refer to Section 5, paragraph 5.1.

mA OUT

RS-485

COMM.

+

-

+

-

ANALOG IN

SENSOR COMMON

OUTDOOR SENSOR IN

REMOTE INTL'K IN

B.M.S. (PWM) IN

SHIELD

+

-

+

-

AUX SENSOR IN

NOT USED

EXHAUST SWITCH IN

DELAYED INTL'K IN

FAULT RELAY

120 VAC, 5A, RES

AUX RELAY

120 VAC, 5A, RES

G

RELAY CONTACTS:

120 VAC, 30 VDC

5 AMPS RESISTIVE

DANGER

120 VAC USED

IN THIS BOX

NOT USED

NOT USED

NC

COM

NO
NC

COM

NO

NOT USED

Figure 2.11

I/O Box Terminal Strip