APPENDIX A

A-5

APPENDIX A -

BOILER MENU ITEM DESCRIPTIONS - CONTINUED

MENU LEVEL & OPTION

DESCRIPTION

TUNING MENU

Prop Band

Generates a valve position based on the error that

exists between the setpoint temperature and the

actual outlet temperature. If the actual error is less

than the proportional band setting (1 to 120°F), the

valve position will be less than 100%. If the error is

equal to or greater than the proportional band

setting, the valve position will be 100%.

Integral Gain

This sets the fraction of the output, due to setpoint

error, to add or subtract from the output each minute

to move towards the setpoint. Gain is adjustable

from 0.00 to 1.00 (Default is 0.10).

Derivative Time

This value (0.0 to 20.0 min.) responds to the rate of

change of the setpoint error. This is the time that

this action advances the output.

Reset Defaults?

Allows Tuning Menu options to be reset to their

Factory Default values.