SAFETY DEVICE TESTING

6-6

6.11 IGNITION SWITCH OPEN DURING

IGNITION

1. Set the unit’s

ON/OFF switch to the OFF

position. Place the unit in manual mode and

set the valve position between 25% and

30%.

2. Remove the air/fuel valve cover (Fig. 6.7) by

rotating the cover counterclockwise to

unlock it then pulling it towards you.

3. Remove one of the two wires from the

ignition switch (Fig. 6.8) and start the unit.

4. The unit should begin to start then shut

down and display IGN SWITCH OPEN

DURING IGNITION.

5. Replace the wire on the ignition switch and

depress the

CLEAR button. The unit should

restart.

6.12 SAFETY PRESSURE RELIEF

VALVE TEST

Test the safety Pressure Relief Valve in accor-

dance with ASME Boiler and Pressure Vessel

Code, Section VI.