Aerco, Appendix g, Legend – AERCO KC1000 Low NOx Boiler July 2011 User Manual
Page 102

APPENDIX G
G-2
CONNECT
5/
8''
I.D
. HOSE TO CONDENSATE DRAIN
SHELL DRAIN VALVE
*
RELIEF VALVE
*
PANELS AND COVERS
.
LOCATE GAS PRESSURE REGULATOR A MINIMUM OF
2'
FROM BOILER
.
5)
LOCATE WATER INLET AND OUTLET FITTINGS
(i.
e.
UNIONS
, ELBOWS
, ETC
.)
AND ALL PIPING A MINIMUM
2)
ALL
(*)
ITEMS ARE INCLUDED SEPARATELY IN SHIPMENT
.
RELIEF VALVE SHOULD BE PIPED VERTICALLY TO A HEIGHT
18
'' ABOVE FLOOR
.
4)
SHELL DRAIN VALVE AND CONDENSATE HOSE SHOULD BE ARRANGED TO PERMIT
NOTES
:
6)
SEE PRODUCT SPECIFICATION FOR PRESSURE DROPS AT VARIOUS FLOWS
.
(NOTE
5)
6''
1)
THIS IS A TYPICAL INSTALLATION DRAWING
.
3)
FOR ACTUAL SIZES AND LOCATIONS OF PIPING AND OTHER
1-
1/
4''
MANUAL SHUTOFF
*
DIRT TRAP
2'
BOILER WATER IN
EXPANSION COMPONENTS
TYPICAL LOCATION OF MAKE
-UP
, ELIMINATION AND
DIAPHRAGM TYPE EXPANSION TANK
PREVENTER
BACKFLOW
COLD WATER IN
FILL VALVE
PRESSURE REDUCING
LINE SIZE BYPASS
AUTOMATIC AIR VENT
AIR
SYSTEM PUMP
SEPARATOR
BOILER WATER OUT
2'-
10
'
HEADER TEMP
.
SENSOR
DRAIN
GAS FIRED BOILER
MULTIPLE UNIT INSTALLATION
CONNECTIONS TO THE BOILER
, SEE DIMENSIONAL DRAWING
.
THE FLUIDS TO DRAIN FREELY
, BY GRAVITY
, TO A CONVIENIENT FLOOR DRAIN
.
OF
6''
FROM BOILER FITTINGS TO PREVENT INTERFERENCE WITH REMOVAL OF BOILER
NORTHVALE
, NJ
07647
INTERNATIONAL
, INC
.
APPD
.
DWN
.BY
SCALE
DATE
CZ
012207
DATE
JK
NTS
012207
AERCO
SD
-A
-712
C
REV
.
CHECK VALVE
STOP VALVE
COMB
. BALANCING
/
Y-
STRAINER
UNION
STOP VALVE
LEGEND
KC
1000 1
MIL
. BTU LOW NOx
LOCAL CODES AND AUTHORITIES SHOULD BE CONSULTED
.
MAINTAIN A REGULATED
8.
8''
W
.C
.
PRESSURE
(NATURAL GAS
)/7
.7
" W
.C
.
(PROPANE GAS
) AT MAXIMUM BTU
/H
INPUT
MANDATORY GAS PRESSURE REGULATOR
(SUPPLIED BY OTHERS
)
(FOR DUAL
-FUEL INSTALLATION
, SEE NOTE
8)
GAS IN
- SEE GF
-1030
FOR GAS PIPING INSTALLATION
(FOR DUAL
-FUEL INSTALLATION
, SEE NOTE
8)
8)
FOR DUAL
-FUEL INSTALLATION
:
- INSTALL APPROPRIATE REGULATOR FOR CURRENT FUEL IN USE
.
- INSTALLER MUST CHECK WITH LOCAL CODES REGARDING ACCEPTABLE METHOD OF DESIGNING DUAL GAS PIPING
SYSTEM TO PREVENT DIRECT FLOW OF FUEL FROM ONE SYSTEM OF GAS PIPING INTO ANOTHER
(FOR EXAMPLE
,
FROM NATURAL GAS TO PROPANE
, AND VICE VERSA
).
7)
BOILERS SHOULD BE PIPED REVERSE RETURN AS SHOWN OR BALANCING DEVICES ON THE OUTLETS
OF THE HEATERS SHOULD BE EMPLOYED
.