Connecting to the alarm port – Cisco XM Universal Gateways Cisco AS5400XM User Manual

Page 41

Advertising
background image

3-11

Cisco AS5400XM Universal Gateway Chassis Installation Guide

OL-6418-02

Chapter 3 Installing the Cisco AS5400XM Universal Gateway

Connecting to the Alarm Port

Figure 3-12

Connecting to the BITS Port

Connecting to the Alarm Port

Connect to the alarm port as follows:

Step 1

Insert the three-pin alarm port connector into the alarm port terminal block. (See

Figure 3-13

.)

Figure 3-13

Connecting to the Alarm Port

Note

Connect the alarm port only to a safety extra-low voltage (SELV) source using 22 AWG, or
thicker, copper wire. SELV ratings are maximum 30 volts AC (RMS), maximum 60 volts DC,
and maximum 50 VA power. The alarm port is rated for 2.0-amp maximum current.

Universal gateway

52503

Coaxial cable

Timing signal

generator

Satellite global

positioning system

35145

Alarm port
connector

Cable ties

#1

#2

#3