ANSI/SIA CP-01 requirements

CP-01 feature descriptions and specifications are listed in Table 9 below. The following are requirements for compliance with

ANSI/SIA CP-01 standards.

Note: Where a conflict exists, UL requirements take precedence over ANSI/SIA requirements.

Minimum system requirements:

One control panel

Two keypads

Do not enable remote arming in SIA classified installations.

Off premise transmission must be in the SIA format.

Do not exceed 1 minute for the abort window and entry delay.

Note: A call-waiting cancel on a noncall-waiting line prevents successful connection to the central station.

Table 9: CP-01 feature descriptions and specifications

CP-O1 feature description

Feature description as shown in
manual

Program
location

Seg/opt Default

CP-01required

setting

Exit 1 delay

24

2

60

45 to 240 seconds

Exit time

Exit 2 delay

24

4

60

45 to 240 seconds

Progress annunciation /
disable - for silent exit

Silent keypad option

93

a

2

All annunciators enabled Allowed (individual

keypads may be disabled)

Exit time restart (reexit)

This feature is not programmable in the panel.

Enabled

Auto stay arm on unvacated
premises

Auto bypass

23

1/3

Enabled

Enabled

Exit time and progress
annunciation/disable for
remote arm

This feature is not programmable in the panel. Exit time and progress are always
enabled.

Enabled (disabled for
remote arming)

Entry 1 delay

24

1

30

30 to 240 seconds

Entry delays

b

Entry 2 delay

24

3

30

30 to 240 seconds

Abort window - for nonfire
zones

Dialer delay

40

8

30

Enabled (may be disabled
by zone/zone type, but no
cancel reports will be sent)

Abort window time - for
nonfire zones

b

Dialer delay

40

8

30

15 to 45 seconds

Abort annunciation

This feature is not programmable in the panel. Flashing cancel LED goes off when
disarming.

Enabled

Cancel annunciation

Cancel 23

3/6

Enabled

Enabled

Duress feature

Duress

44

Disabled

Disabled

Two trips on cross zone

37

5/4

Disabled

Required

Keypad sounds on cross zone trip 39

5

Disabled

Cross zoning

Zone type characteristic

111

3/4

Disabled

Programmable cross zoning
time

Cross zone time

40

6

5 minutes

Allowed

Swinger shutdown

Swinger shutdown count

38

n/a

n/a

For all nonfire zones, shut
down at 1 to 2 trips

Swinger shutdown disable

Swinger shutdown count

38

n/a

Enabled for 1 trip

Allowed

Fire alarm verification

Fire alarm verification time

40

9

Enabled for 1 trip

Required (depends on
panel and sensors)

10

NX-8V2 Control Panel Installation Instructions