Terminal Description

KP POS

Connect to the POS terminal on the keypads and the
expanders. Individually, this terminal is limited to 1 amp.
Combined, this terminal and AUX PWR+ are limited to 2
amps total current.

SMOKE+

Smoke detector power 12 VDC, 1.5 amps maximum (for
those jurisdictions which allow the Priority zone to be used
with smoke detectors).

COM

Common negative wire of powered devices such as
motion detectors and smoke detectors.

AUX
PWR +

Connect positive wire of all powered devices except
smoke detectors and keypads. Individually, this terminal is
limited to 1 amp. Combined, this terminal and KP POS are
limited to 2 amps total current.

ZONE8

Connect to one side of zone 8 loop. Connect the other
side to com terminal. Open or short causes alarm. Only
zone 8 may be used for a two-wire smoke detector using
a 680 ohm EOL resistor. Refer to the wiring diagram.
Program location 37, segment 6, option 1.

COM

Common (-) terminal for zones 7 and 8.

ZONE7

Connect to one side of zone 7 loop. Connect the other
side to COM terminal. Open or short causes alarm.

ZONES 6
to 1

Connect as described for zones 7 and 8. Only zone 8 can
be a two-wire zone. Refer to the wiring diagram for
examples.

AUX1 to
AUX4

Connect negative lead of low current device [relay, LED
(install 1kohm resistor in series with LED), etc.] Connect
positive lead of device to COM. Current is limited to 50
mA when output is negative, and 250 uA when output is
positive.

Module list

Table 3 below shows the modules that are compatible with the

NX-8V2 system. Additional information and a catalog listing all

system components is available from Customer Support

Table 3: Modules that can be added to the NX-8V2

Terminal Description

NX-108E

8-zone LED keypad

NX-116E

16-zone LED keypad

NX-124E

24-zone LED keypad

NX-148E

Alphanumeric 48-zone LCD keypad

NX-148E-
RF

b

Alphanumeric 48-zone LCD keypad with built-in 48-zone
wireless receiver

NX-200

a

Zone doubling kit (includes one hundred 3.74k and one
hundred 6.98k resistors)

NX-320E

Smart power supply and bus extender

NX-408E

8-zone wireless expansion module (UL listed part #60-
904)

NX-416E

16-zone wireless expansion module (UL listed part #60-
904)

Terminal Description

NX-448E

48-zone wireless expansion module (UL listed part #60-
904)

NX-508E Eight-output

module

NX-534E

Two-way listen-in module

NX-540E

a

Operator telephone interface module

NX-548E

b

48-zone

wireless

receiver

NX-591E-
GSM

a

Cell interface

NX-
1192E

192-zone LCD keypad

NX-
1208E

8-zone LED keypad

NX-
1248E

48-zone LCD keypad

NX-
1308E

8-zone LED door design keypad

NX-
1316E

16-zone LED door design keypad

NX-
1324E

24-zone LED door design keypad

NX-
1448E

48-zone fixed language icon keypad

a> These products have not been tested and approved by
Underwriters Laboratories, In.

b> These wireless devices are UL listed only for residential
applications.

Note: The NX-8V2 control panel sends a trouble condition

once each hour if it senses that no devices have been enrolled.

This report shows expander trouble--device zero (0).

Control panel programming

Programming the control panel requires you to enter program

mode, select the module to program, program a location, and

then exit the location and program mode.

Enter program mode

T

o enter program mode, do the following:

1. Press

8. The five function LEDs (Stay, Chime, Exit,

Bypass, and Cancel) begin flashing.

2. Enter the go to program

code (default is 9, 7, 1, 3). If the

go to program code entry is valid, the Service LED flashes,
and the five function LEDs illuminate. You are now in

program mode and can select the module to program.

2

NX-8V2 Control Panel Installation Instructions