Interlogix NX-1710E User Manual

Page 15

Advertising
background image

NX-1710E Single Door Control

15

L

OCATION

4 P

ROGRAMMING THE

Z

ONES

(2 segments of numerical data)

Segment 1

Door Shunt Zone

Program the zone that will be monitored as a door for access control. This location must be programmed with a
valid zone for monitored access control functions to work properly. (Default is 0)

Additionally, this zone must be configured in the control panel as a Door Shunt zone by

programming an unused Zone Type Characteristic in locations 111-169 (Seg 4, Opt 4).

Segment 2

Request To Exit (RTE) Zone

Program the zone that will be monitored to signal an RTE. If this segment is programmed with a valid zone and
the zone is faulted, the reader will activate its onboard relay and send the RTE. (Default is 0)

Additionally, this zone must be configured in the control panel as an RTE zone by

programming an unused Zone Type Characteristic in locations 111-169 (Seg 4, Opt 3).

L

OCATION

5 P

ROGRAMMING THE

V

ARIOUS

R

EADER

T

IMERS

(4 segment of numerical data)

Segment 1

Scan Time

Enter the amount of time required to hold a card between beeps to activate the functions programmed in
Location 0, Segments 2 and 3. This timer is timed in 1/100-second increments from 0 to 2.55 seconds. (Default
is 100 = 1 second).

Segment 2

Relay Active Time

Enter the amount of time the onboard relay is energized once activated. This timer is timed in 1-second
increments from 0 to 255 seconds. (Default is 10 = 10 seconds).


Segment 3

Door Fault Warning Time

Enter the amount of time a monitored zone (see Location 4, Segment 1) must be faulted before sounding a
warning (local buzzer). The door fault warning is timed in 1-second increments from 0 to 255 seconds. (Default
is 30 = 30 seconds).

Segment 4

Door Fault Alarm Time

Enter the amount of time a monitored zone (see Location 4, Segment 1) must be faulted before sending an
alarm condition to the control panel. The door fault alarm is timed in 1-second increments from 0 to 255
seconds. (Default is 60 = 60 seconds).

L

OCATION

6 P

ROGRAMMING THE

O

PENING

T

IME FOR

S

CHEDULE

1

(2 segments of numerical data)

Segment 1

Program the hour of the opening time in 24-hour format. (Default is 8 = 8:00 AM)

Segment 2

Program the minutes after the hour of the opening time for Schedule 1. (Default is 0)

L

OCATION

7 P

ROGRAMMING THE

C

LOSING

T

IME FOR

S

CHEDULE

1

(2 segments of numerical data)

Segment 1

Program the hour of the closing time in 24-hour format. (Default is 20 = 8:00 PM)

Segment 2

Program the minutes after the hour of the closing time for Schedule 1. (Default is 0)