TruPortal Software User Guide

97

Diagnostics

•

An ellipsis (...) appears if additional information about a category is available in a tool tip that
can be displayed by hovering over the ellipsis.

•

The System does not include actions for running specific diagnostic tests.

•

Click [Download Diagnostic File] to create a single, encrypted file that includes a variety of
system information, including configuration data and logs. No specific personnel information
(for example, names or Social Security numbers) will be included in the file; refer to the Release
Notes for details. The file can be saved locally and sent to Technical Support for use in
troubleshooting issues.

•

An accurate reading for DC current cannot be displayed when the System Controller is powered
by a DC source. The DC current information is only displayed when the System Controller has
AC power.

Diagnostic

Display Value

Status

AC Power

OK | Brownout | Fail

INF = OK

WRN = Brownout

ERR = Fail

DC Power

Voltage, Current

INF >= 10.0

VWRN < 10.0 V

WRN = Current overload

Backup Battery

Voltage, Current, Charging | Discharging

INF >= 11.7

VWRN < 11.7 V

ERR < 11.4 V, No Battery

Memory Battery

Voltage

INF >= 2.3 V

WRN < 2.3 V

ERR < 2.0 V

Fuses

OK | Fuse Name,…

INF = All OK

ERR = If any not OK

Controller

OK | Problems,…

INF = OK

WRN = If not OK

Modules

OK | ModuleName problem,…

INF = All OK

WRN = If any tamper

ERR = If any offline

Doors

OK | DoorName problem,…

INF = All OK

WRN = If any held,
forced, tamper

ERR – If any offline

Digital Inputs

OK | InputName problem,…

INF = All OK

WRN = If any tamper

ERR – If any offline

Uptime

Last boot time, up days

INF = Always

CPU Load Avg

1m, 5m, 15m

INF 15m < 0.80

WRN 15m >= 0.80

ERR 15m >= 0.95