Hardware problem states, Troubleshooting readers, Hardware problem states troubleshooting readers – Interlogix TruPortal User Manual

Page 111

Advertising
background image

TruPortal Software User Guide

99

Diagnostics

Hardware Problem States

Hardware items can have the following problems:

Controller

Tamper

Modules

Offline

Tamper

Doors

Offline

Forced

Held

RTE Tamper

Door Contact Tamper

Door Aux Tamper

Door Tamper

Digital Input

Offline

Tamper

Troubleshooting Readers

If a reader is not responding as desired, use the [Scan for Hardware Changes] button (see

Scan for

Hardware Changes

on page 22), verify that the reader appears in the Device Tree hierarchy on the

System Administration > Devices page, and check the reader configuration. See

Configure Readers

on page 32.

If unexpected events occur for doors or readers connected to an IPSDC, check the IPSDC jumper and
switch settings to make sure that the hardware is configured correctly. For example, the reader Device
Input (DI) port, J2, has two digital inputs which are used for door status devices (door contacts and
exit request input) and can be configured as either supervised or non-supervised digital inputs. If the
inputs are configured as supervised digital inputs in the TruPortal User Interface, they require EOL
resistors. Refer to the IPSDC Quick Reference for details.

Aux 2

CN3.3

CN3.4

Door Controller

CN10.2

CN17.2

CN11.4

CN18.4

Aux Input

CN21.1

CN21.3

CN22.2

Fuse

+V

0V

Advertising