Troubleshooting Schedules

If a schedule is not behaving as expected, review the following sections:

Creating Holiday Groups

on page 38

Creating Schedules

on page 40

Considerations for Schedule-Based Action Trigger Records

on page 55

Error, Warning and Event Messages

Tamper States

The System Controller does not distinguish which of the four door input are in tamper state when it
logs tamper events. The real-time state of inputs in tamper can be viewed on the Monitoring >
Diagnostics
page.

Power and Battery Events

System Controller Shuts Down on Battery Power

If the System Controller is operating on battery power only and the battery voltage drops below 10.2
volts, the System Controller will shut down until AC power is restored.

Backup Battery Events

Backup Battery Events occur when the backup battery voltage drops below certain thresholds.

Note:

If the System Controller is powered exclusively off of a backup battery, it will shutdown
at 10.2V and the Cutoff and Not Detected events will not be generated.

Memory Battery Event

Event Code

Event Description

Cause

Event 14612

Backup Battery Critical

Voltage falls below 11.4V, or rises above 10.2V

Event 14613

Backup Battery Cutoff

Voltage falls below 10.2V, or rises above 9.0V

Event 14624

Backup Battery Low

Voltage falls below 11.7V, or rises above 11.4V

Event 14625

Backup Battery Restored

Voltage rises above 11.7V

Event 14649

Backup Battery Not Detected

Voltage falls below 9.0V

Event Code

Event Description

Event 14618

Memory Backup Battery Low