8.2 DDC Controls,

Options D10 and

D14 (ONLY for

sizes 150-400)

FIGURE 15A -

DDC Control with

Transformer and

Relays is Mounted on

a Specially Designed

Bracket in the Control

Compartment

If the heater was ordered with Option D10 or D14, it is equipped with a Novar Minio

control module. The Novar control with its accompanying relays and power transformer

are mounted in the control compartment of the unit. See

FIGURE 15A. This control

offers a wide variety of input and output points that can be configured to meet a wide

range of building management applications. User-selectable input types are Thermis-

tor, 4-20 milliamp, 1-5 volts, or digital.

Control

Option D10 includes the controller and the sensor to be field mounted at the

heater discharge.

Option D14 requires a field-supplied sensor that is compatible with

the control. For regulatory compliance specifications, and safety precautions, review

the control manufacturer’s installation instructions in the owner’s envelope.
The recommended location for mounting the sensor is on the side of a field-installed

optional downturn nozzle. See

FIGURE 15B for an illustration of the sensor included

with Option D10 and dimensions for mounting it on the nozzle side.

Center the

1” (25mm)

sensor hole

vertically on

the nozzle

side.

2-1/4”

(57mm)

2-1/4”

(57mm)

(76mm)

9/16”

(14mm)

9/16”

(14mm)

Ø 1”

(25mm)

Nozzle flange

that connects

to the heater

outlet.

Ø (4) 1/8”

(3mm)

Before installing the

discharge nozzle, drill

the holes in the side

panel as illustrated.

Mount the sensor on the nozzle side.
Drill a 7/8” hole in the cabinet top above the controller and install the bushing supplied

with the unit for running the sensor wire. Wire the sensor to the controller as illustrated

on the wiring diagram on the heater. Sensor wire is field-supplied.

FIGURE 15B -

Recommended

Location for Mounting

the Sensor is on

the Side Panel of a

Discharge Nozzle

(Option CD 2, 3, or 4)