Clearances and dimensions, 1 clearances, 0 clearances and dimensions – Reznor UDAS Unit Installation Manual User Manual

Page 7: Clearances, Instructions for changing pressure switch, Pressure switch, Downturn nozzle kits, option cd 2, 3, or 4, Figure 3

Advertising
background image

Page 7

4.0 Clearances

and

Dimensions

Clearances

Size

Top

Flue Connector

Access Panel

Non-Access Side

Bottom*

Rear**

inches

mm

inches

mm

inches

mm

inches

mm

inches

mm

inches

mm

30 - 125

1

25

6

152

18

457

1

25

1

25

18

457

150 - 400

4

102

6

152

18

457

2

51

1

25

18

457

*Suspend the heater so that the bottom is a minimum of 5 feet (1.5M) above the floor.

** Measure rear clearance from the fan motor.

4.1 Clearances

Units must be installed so that the clearances in the table are provided for combustion

air space, inspection and service, and for proper spacing from combustible construc-

tion. Clearance to combustibles is defined as the minimum distance from the heater

to a surface or object that is necessary to ensure that a surface temperature of 90°F

(50°C) above the surrounding ambient temperature is not exceeded.

FIGURE 2 -

Installing High

Altitude Pressure

Switch required

above 6000 ft

(1830M) elevation

Gas valve adjustment

for high altitude can

only be done after

heater is operating;

see Paragraph 6.1.

Instructions for Changing Pressure Switch

1. In the control compartment, locate the pressure switch.

2. Mark and disconnect the two wires attached to the pressure switch.

3. Disconnect the sensing tubes from the pressure switch.

4. Locate the two screws holding the switch mounting bracket. Remove the screws and the pressure switch. Save

the screws.

5. Using the same screws, install the high altitude pressure switch. Attach the sensing tubes and wires.

Pressure Switch

Standard Power Vent Models
Size

30

45

60 75

100

125

150 175 200 225 250 300 350 400

High Altitude Switch P/N

197031

197032

197031

201160

Negative Pressure OFF Setpoint "w.c.

0.35

0.45

0.35

1.05

Label color

Purple

Pink

Purple

Brown

Standard Power Vent Models with Option AV6 for Common Venting
Size

30

45

60 75

100

High Altitude Switch P/N

197029 197032 196362 196388

Negative Pressure OFF Setpoint "w.c.

0.60

0.45

0.55

0.50

Label color

Lt Blue

Pink

White Orange

Separated Combustion Models
Size

30

45

60 75

100

125

150 175 200 225 250 300 350 400

High Altitude Switch P/N

197029

196388 197030 197031

201160

Differential Pressure OFF Setpoint "w.c.

0.60

0.50

0.40

0.35

1.05

Label color

Lt. Blue

Orange Green

Purple

Brown

Adjusting the valve outlet pressure is done after the heater is in operation; follow the

instructions in Paragraph 6.1

.

Capacities and inputs for derated units are also listed in

Paragraph 6.1.
If the pressure switch needs to be changed, do that before the heater is operated; fol-

low the instructions in

FIGURE 2.

Downturn Nozzle Kits,

Option CD 2, 3, or 4

(Does not apply to Model APD)

Follow the instructions with the kit to install. Additional length beyond the front of the

unit is shown in

FIGURE 3.

FIGURE 3 -

With Optional

Downturn Nozzle

Dimension “U”

-- Applies to Standard

Power Vent (except APD)

& Separated Combustion

Models

Size

Options CD2 and CD4

Option CD3

inches

mm

inches

mm

30, 45

7-1/8

181

12-3/8

314

60, 75

8-5/8

219

15

381

100, 125

12-5/8

321

21-7/8

556

150, 175, 200

11-1/2

292

19-7/8

505

225, 250

14-1/2

368

25-1/8

638

300, 350, 400

18-1/2

470

32

813

In addition, if the heater is being installed at an altitude above 6000 ft (1830M), the

pressure switch will have to be changed. If ordered with the unit as Option DJ20 or

DJ21, the pressure switch is shipped separately for field installation.

Advertising