3 check installation after startup – Reznor UDAS Unit Installation Manual User Manual

Page 27

Advertising
background image

Page 27

Operating Sequence

1. Set thermostat at lowest setting.

2. Turn off all electric power to the appliance.

3. This appliance is equipped with an ignition device which automatically lights the

burner. Do not try to light the burner by hand. Open the access door and locate the

gas control (ON/OFF) knob or switch on the gas valve. (See

FIGURE 17.)

4. Turn the gas control switch to “OFF” or the knob clockwise to “OFF”.

5. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the

floor.

If you smell gas, STOP! and follow the steps in the WARNINGS printed

above or on the Operating Label on the heater. If you do not smell gas, proceed to

the next step.

6. Turn the gas control switch to “ON” or the knob counterclockwise to “ON”.

7. Close the access door.

8. Turn on the electric power to the heater.

9. Set the thermostat to the desired setting.
NOTE: If the appliance does not operate, follow the instructions “To Turn Off Gas to

Appliance” printed below (and on the Operating Label on the heater) and call your

service technician.

10. Thermostat calls for heat, energizing the venter motor.

11. Venter pressure switch closes, firing the unit.

12. Burner flame is sensed and in 30 seconds after the gas valve is energized, the

fan motor is energized.

13. If the flame is extinguished during the main burner operation, the integrated con-

trol system closes the main valve and must be reset by interrupting power to the

control circuit. (See lighting instructions on the heater.).

TO TURN OFF GAS TO THE APPLIANCE

1) Set thermostat to lowest setting

2) If service is to be performed, turn off all electric power to the appliance.

3) Open the access door.

4) Turn the gas control switch to “OFF” or turn knob clockwise to “OFF” (Do not

force).

5) Close the access door.

Gas Control

Knob

(shown

in the ON

position)

Gas

Flow

Gas

Flow

Top View

Side View

FIGURE 17 - Gas Valve

9.3 Check

installation after

startup:

Vent System Testing Procedure

The steps below shall be followed with each heater or utility heater connected to the

venting system placed in operation while any other appliance(s) connected to the vent-

ing system(s) is not in operation.
1. Seal unused openings(s) in the venting system.
2. Inspect the venting system for proper size and horizontal pitch as required in the

National Flue Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane

Installation Code, CSA B149.1, and the venting manual instructions. Verify that

there is no blockage or restriction, leakage, corrosion, and/or other deficiencies

that could cause an unsafe condition.

3. In so far as is practical, close all doors, windows, other open spaces within the

building, and all doors between the space in which the appliance(s) connected to

the venting system is located. Turn on clothes dryers and any exhaust fans (such

as range hoods and bathroom exhausts) so they operate at maximum speed. Do

not operate a summer exhaust fan. Close fireplace dampers.

4. Following the lighting instructions, place the utility heater being inspected in

operation. Adjust the thermostat so that the utility heater will operate continuously.

5. After it has been determined that each utility heater connected to the venting

system properly vents when tested as outlined above, return doors, windows,

exhaust fans, fireplace dampers, and any other gas-burning appliance to their

previous condition of use.

6. If improper venting is observed during any of the above tests, the venting system

must be corrected.

Top View

ON/OFF Switch

Advertising
This manual is related to the following products: