2 location recommendations, Warning – Reznor UDAS Unit Installation Manual User Manual

Page 5

Advertising
background image

Page 5

Locate the heater so that it is a minimum of five feet (1.5M) above the floor and in

compliance with the clearances in Paragraph 4.1.

WARNING

If touched, the vent pipe and internal heater surfaces that are

accessible from outside the heater will cause burns. Suspend the

heater a minimum of 5 feet (1.5M) above the floor.

For best results, the heater should be placed with certain rules in mind. In general, a

unit should be located from 8 to 12 feet (2.4-3.7M) above the floor. Units should always

be arranged to blow toward or along exposed wall surfaces, if possible. Where two or

more units are installed in the same room, a general scheme of air circulation should

be maintained for best results.
Suspended heaters are most effective when located as close to the working zone as

possible, and this fact should be kept in mind when determining the mounting heights

to be used. However, care should be exercised to avoid directing the discharged air

directly on the room occupants.
Partitions, columns, counters, or other obstructions should be taken into consideration

when locating the unit heater so that a minimum quantity of airflow will be deflected by

such obstacles.

2.2 Location Recommendations

Dimensions X, Y, and Z (feet) Models with Standard Horizontal Louvers at Mounting Heights of 5 - 18 ft

H

30

45

60

75

100

125

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

5 ft

6

14

30 -21°

7

16

40 -20° 8 18 45 -16°

9

20

57 -14°

9

20

59

-18° 10 22

65

-14°

8 ft

7

13

26 -39°

9

16

37 -34° 10 18 42 -29° 12 22

54 -25° 11 21

56

-28° 12 23

63

-24°

10 ft

6

11

22 -52°

9

15

33 -43° 10 17 39 -37° 12 22

52 -32° 12 20

52

-36° 13 24

60

-30°

12 ft

-

-

-

-

8

12

27 -55° 10 16 34 -46° 12 21

48 -39° 11 19

47

-44° 14 23

57

-36°

14 ft

-

-

-

-

-

-

-

-

9 14 29 -56° 12 19

44 -46° 11 17

42

-51° 14 22

53

-43°

16 ft

-

-

-

-

-

-

-

-

-

-

-

-

11 17

38 -54° 10 14

34

-58° 13 20

47

-50°

18 ft

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

11 17

40

-57°

H

150

175

200

225

250

300

350

400

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

8 ft

13 24

73 -26° 15 28

90 -22° 16 30 93 -20° 14 27

86 -24° 16 29

93

-21° 15 28

94

-24° 17 31 105 -20° 18 34 113 -17°

10 ft 14 24

69 -32° 17 29

87 -27° 17 31 91 -25° 15 27

82 -30° 17 30

90

-26° 16 28

89

-29° 18 32 103 -25° 20 35 110 -21°

12 ft 14 24

64 -39° 18 29

84 -32° 18 31 88 -30° 16 27

78 -35° 18 30

87

-31° 17 28

85

-34° 19 32

98 -30° 21 36 108 -25°

14 ft 14 22

59 -45° 18 28

79 -37° 19 30 84 -34° 16 26

73 -41° 18 30

83

-36° 17 27

80

-40° 20 32

95 -34° 23 35 105 -29°

16 ft 13 20

53 -51° 18 27

74 -42° 19 29 79 -39° 16 24

67 -47° 19 28

78

-41° 17 25

74

-45° 21 31

90 -38° 23 35 101 -33°

18 ft 11 17

44 -58° 17 26

68 -48° 19 28 74 -44° 14 22

60 -53° 18 27

72

-46° 16 24

66

-51° 20 30

85 -43° 23 35

97 -37°

Dimensions X, Y, and Z (meters) Models with Standard Horizontal Louvers at Mounting Heights of 1.5 - 5.5M

H

30

45

60

75

100

125

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

1.5 M 1.8 4.3 9.1 -21° 2.1 4.9 12.2 -20° 2.4 5.5 13.8 -16° 2.7 6.1 17.4 -14° 2.7 6.1 18.0 -18° 3.0 6.7 19.9 -14°
2.4 M 2.1 4.0 7.9 -39° 2.7 4.9 11.3 -34° 3.0 5.5 12.8 -29° 3.7 6.7 16.5 -25° 3.4 6.4 17.1 -28° 3.7 7.0 19.2 -24°
3.0 M 1.8 3.4 6.7 -52° 2.7 4.6 10.0 -43° 3.0 5.2 11.9 -37° 3.7 6.7 15.8 -32° 3.7 6.1 15.8 -36° 4.0 7.3 18.3 -30°
3.7 M -

-

-

-

2.4 3.7 8.2 -55° 3.0 4.9 10.4 -46° 3.7 6.4 14.6 -39° 3.4 5.8 14.3 -44° 4.3 7.0 17.4 -36°

4.3 M -

-

-

-

-

-

-

-

2.7 4.3 8.8 -56° 3.7 5.8 13.4 -46° 3.4 5.2 12.8 -51° 4.3 6.7 16.1 -43°

4.9 M -

-

-

-

-

-

-

-

-

-

-

-

3.4 5.2 11.6 -54° 3.0 4.3 10.4 -58° 4.0 6.1 14.3 -50°

5.5 M -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

3.4 5.2 12.2 -57°

H

150

175

200

225

250

300

350

400

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

2.4 M 4.0 7.3 22.3 -26° 4.6 8.5 27.4 -22° 4.9 9.1 28.0 -20° 4.3 8.2 26.2 -24° 4.9 8.8 28.3 -21° 4.6 8.5 28.7 -24° 5.2 9.4 32.0 -20° 5.5 11.3 34.4 -17°
3.0 M 4.3 7.3 21.0 -32° 5.2 8.8 26.6 -27° 5.2 9.4 27.7 -25° 4.6 8.2 25.0 -30° 5.2 9.1 27.4 -26° 4.9 8.5 27.1 -29° 5.5 9.8 31.4 -25° 6.1 10.7 33.5 -21°
3.7 M 4.3 7.3 19.5 -39° 5.5 8.8 25.6 -32° 5.5 9.4 26.8 -30° 4.9 8.2 23.8 -35° 5.5 9.1 26.5 -31° 5.2 8.5 25.9 -34° 5.8 9.8 29.9 -30° 6.4 11.0 32.9 -25°
4.3 M 4.3 6.7 18.0 -45° 5.5 8.5 24.1 -37° 5.8 9.1 25.6 -34° 4.9 7.9 22.3 -41° 5.5 9.1 25.3 -36° 5.2 8.2 24.4 -40° 6.1 9.8 29.0 -34° 7.0 10.7 32.0 -29°
4.9 M 4.0 6.1 16.2 -51° 5.5 8.2 22.6 -42° 5.8 8.8 24.1 -39° 4.9 7.3 20.4 -47° 5.8 8.5 23.8 -41° 5.2 7.6 22.6 -45° 6.4 9.4 27.4 -38° 7.0 10.7 30.8 -33°
5.5 M 3.4 5.2 13.4 -58° 5.2 7.9 20.7 -48° 5.8 8.5 22.6 -44° 4.3 6.7 18.3 -53° 5.5 8.2 21.9 -46° 4.9 7.3 20.1 -51° 6.1 9.1 25.9 -43° 7.0 10.7 26.9 -37°

NOTE: Venting

requirements may

affect location.

Consult the Venting

Manual for this heater

before making final

determination.