Appendix – Reznor UDAS Unit Installation Manual User Manual

Page 38

Advertising
background image

Page 38

APPENDIX

TECHNICAL DATA - Sizes 150 - 400 (Data applies to all Models unless noted otherwise.)
Size

150

175

200

225

250

300

350

400

Input Heating Capacity

BTUH

150,000 175,000 200,000 225,000 250,000 300,000 350,000 400,000

kw

43.9

51.2

58.6

65.9

73.2

87.8

102.5

117.1

Thermal Efficiency (%)

83

83

83

83

83

83

83

83

Output Heating Capacity

A

BTUH

124,500 145,250 166,000 186,750 207,500 249,000 290,500 332,000

kw

36.4

42.5

48.6

54.7

60.8

72.9

85.1

97.2

Gas Connection (inches)

B

Natural

1/2

1/2

1/2

3/4

3/4

3/4

3/4

3/4

Propane

1/2

1/2

1/2

3/4

3/4

3/4

3/4

3/4

Vent Connection

C

(inches diameter)

5

5

5

5

5

6

6

6

Combustion Air Inlet

C

(inches diameter) -

Separated Combustion only

6

6

6

6

6

6

6

6

Control Amps (24 volt)

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Full Load Amps (115 volt)

3.8

3.8

4.6

7.5

7.5

10.7

10.7

10.7

Maximum Over Current

Protection

D E

Standard 115V

15

15

15

15

15

20

20

20

Optional 208V or 230V

15

15

15

15

15

15

15

15

Normal Power Consumption (watts)

392

392

491

747

747

1086

1086

1086

Discharge Air Temperature Rise (°F)

60

60

60

60

60

60

60

60

Air Volume

CFM

1921

2242

2562

2882

3202

3843

4483

5123

M

3

/minute

54.4

63.5

72.5

81.6

90.7

108.8

126.9

145.1

Discharge Air Opening Area

ft

2

2.6

2.6

2.6

3.5

3.5

4.8

4.8

4.8

M

2

0.2

0.2

0.2

0.3

0.3

0.5

0.5

0.5

Output Velocity

FPM

752

877

1003

820

911

802

936

1069

M/minute

229

267

306

250

278

244

285

326

Fan Motor HP

E

Standard Open

1/6

1/6

1/6

1/4

1/4

1/2

1/2

1/2

Optional Enclosed

1/4

1/4

1/4

1/4

1/4

1/2

1/2

1/2

Fan Motor RPM

1050

1050

1050

1050

1050

1050

1050

1050

Fan Diameter (inches)

18

18

18

20

20

24

24

24

Sound Level

dba @ 15 ft

51

52

53

56

56

59

61

62

TECHNICAL DATA - Sizes 30 - 125 (Data applies to all Models unless noted otherwise.)
Size

30

45

60

75

100

125

Input Heating Capacity

BTUH

30,000

45,000

60,000

75,000 105,000 120,000

kw

8.8

13.2

17.6

22.0

30.8

35.2

Thermal Efficiency (%)

82

83

83

83

83

83

Output Heating Capacity

A

BTUH

24,600

37,350

49,800

62,250

87,150

99,600

kw

7.2

11.0

14.6

18.3

25.6

29.2

Gas Connection (inches)

B

Natural

1/2

1/2

1/2

1/2

1/2

1/2

Propane

1/2

1/2

1/2

1/2

1/2

1/2

Vent Connection

C

(inches diameter)

4

4

4

4

4

4

Combustion Air Inlet

C

(inches diameter) -

Separated Combustion only

4

4

4

4

4

4

Control Amps (24 volt)

1.0

1.0

1.0

1.0

1.0

1.0

Full Load Amps (115 volt)

1.9

2.4

2.4

3.3

3.9

5.1

Maximum Over Current

Protection

D E

Standard 115V

15

15

15

15

15

15

Optional 208V or 230V

15

15

15

15

15

15

Normal Power Consumption (watts)

109

155

155

217

276

354

Discharge Air Temperature Rise (°F)

50

55

60

60

60

60

Air Volume

CFM

456

629

769

961

1345

1537

M

3

/minute

12.9

17.8

21.8

27.5

36.7

45.9

Discharge Air Opening Area

ft

2

1.0

1.0

1.2

1.2

2.0

2.0

M

2

0.1

0.1

0.1

0.1

0.2

0.2

Output Velocity

FPM

475

656

616

770

668

763

M/minute

145

200

188

238

196

245

Fan Motor HP

E

Standard Open

0.0

0.0

0.0

0.1

1/30

1/20

Optional Enclosed

N.A.

N.A.

N.A.

N.A.

1/4

1/4

Fan Motor RPM

1550

1550

1550

1550

1050

1050

Fan Diameter (inches)

10

10

12

12

16

16

Sound Level

dba @ 15 ft

40

40

40

49

54

55

A

CSA ratings for altitudes to 2000 ft.

B

Size shown is for gas connection to a single-stage gas valve, not supply line size.

C

Smaller and/or larger vent and combustion air pipe diameters may be permissible. For Separated Combustion models refer to the Venting

Installation Manual for Separated Combustion Units. For Standard Power Vent models refer to the Venting Installation Manual for Power Vented

units. For a Standard Power Vent model with Option AV6, refer to the Venting Installation Manual for Common Venting.

D

MOCP = 2.25 x (largest motor FLA) + smallest motor FLA. Answer is rounded to the next lower standard circuit breaker size.

E

Except where indicated, information in this table is based on a heater equipped with a standard 115 volt open fan motor.

Advertising