2 maintenance procedures, Caution: use of eye protection is recommended – Reznor UDAS Unit Installation Manual User Manual

Page 30

Advertising
background image

Page 30

10.2 Maintenance

Procedures

10.2.1 Heat

Exchanger

Maintenance

Remove any external dirt or dust accumulation. Visually check the heat exchanger for

cracks and holes. If a crack or hole is observed, replace the heat exchanger.
NOTE: Inspection of the lower portion of the heat exchanger is done with the burner

removed. See the Burner Service section below for information on inspecting the lower

portion of the heat exchanger.

10.2.2 Burner

Maintenance

If there is an accumulation of dirt, dust, and/or lint, clean the compartment and follow

the instructions below to remove and clean the burner.

CAUTION: Use of eye protection is recommended.

Burner Removal

Instructions (Refer to

FIGURE 19.)

1. Outside the cabinet, shut the gas supply off at the manual valve ahead of the

union.

2. Turn off electric supply.

3. Disconnect the gas supply at the union outside of the cabinet.

4. Remove the access panel.

5. Disconnect and Move the Gas Train - At the gas valve, mark and disconnect the

wires. Carefully remove the burner orifice and orifice adapter locking nut. Slide the

orifice adapter out through the bracket on the burner pushing the gas train to the

right. This will move the gas train out of the way.

6. Move the Control Assembly - Remove the two screws holding the control

assembly bracket. Being careful not to disconnect any wires, slide the control

assembly to the right.

7. Remove Secondary Air Baffles (Sizes 60-400 only) - Vertical along the right side

of the burner, locate the flat plate(s) identified as the secondary air baffle(s). The

quantity of baffles could be one to four depending on heater size. Each baffle is

held in place by one screw.

For re-assembly, on the secondary air shield, mark

the location (top and bottom) of each baffle. Remove all baffles.

8. Remove Burner Assembly

a) Locate the burner body supports. Depending on the size, the burner will have

two or more supports. At each support, remove the one screw that attaches it to

the secondary air shield

b) Holding the venturi tube, slide the entire burner assembly slightly to the right to

disengage the burner from the supports on the left. Then rotate the open end

of the venturi tube inward toward the heater. Carefully pull the burner assembly

out of the cabinet.

Venturi Tube

Orifice Adapter Locking Nut

Slide right; rotate

inward; pull out

Gas Valve

Burner

Orifice

Burner

Assembly

Secondary Air Baffle (Qty varies

per size.) Mark locations before removing.

Control Bracket Screws - Loosen bracket; slide right.

Slide Right

Secondary

Air Shield

Burner Body Support (at least two per unit) - Remove screw attaching

to secondary air shield. Support remains attached to burner.

Disconnect gas train

at orifice and outside

the heater; slide to the

right.

FIGURE 19 - Burner

Removal (Standard

Power Vent model

illustrated; same

process for both

Standard Power

Vent and Separated

Combustion

models)

Advertising
This manual is related to the following products: