6.2.1 Outside Air Hood or Indoor Filter Cabinet

6.2 Unit Inlet Air

A

B

C

G

H

D

E

F

1-1/4 (32)

19-1/

2

(495)

3 (76)

Option AS2, Outside Air Hood

Option AS6, Outside Air Hood with

1" Filters

Option AS7, Outside Air Hood with

2" Filters

Option AW3, Indoor Filter

Cabinet with 1" Filters
Option AW6, Indoor Filter

Cabinet with 2" Filters

FIGURE 9 -

Dimensions

and Weights

Dimensions

Size

1-20, 1-40, 1-50, 1-65

2-80, 2-120

3-180, 3-260

inches

mm

inches

mm

inches

mm

A

38

965

62

1575

74-1/4

1886

B

55

1397

54

1372

64

1626

C

36

914

47-1/2

1207

61-3/8

1559

D

35-9/16

903

59-9/16

1513

71-9/16 1818

E

33-1/8

841

44-5/8

1133

58-1/2

1486

F

19-1/2

495

19-1/2

495

19-1/2

495

G (Duct Connection)

32-15/16

837

56-15/16

1446

69-3/8

1762

H (Duct Connection)

30-3/8

772

41-7/8

1064

57-7/16 1459

Weights and Filter Sizes

Model Sizes

Fltr

Qty

AS6, AW3 AS7, AW6

AS2

AS6

AS7

AW3

AW6

Filter Size

lbs

kg

lbs

kg

lbs

kg

lbs

kg

lbs

kg

1-20, 1-40, 1-50, 1-65

3

12x35x1

12x35x2 225 102 250 113 270 122 100

45

120

54

2-80, 2-120

4

12x35x1

12x35x2 310 141 350 159 380 172 150 68 180 82

4

12x24x1

12x24x2

3-180, 3-260

12

12x35x1

12x35x2 400 181 450 204 490 222 200

91

240 109

Installation Instructions for Optional Screened Air Hood for Outdoor Units (Options AS2,

AS6, AS7) and Filter Sections for Indoor Units (Options AW3, AW6)

All of these air inlet accessories are designed to be attached directly to the system

cabinet. To prevent damage, it is recommended that the system be set in its permanent

location before installing the air hood or filter cabinet option. All are shipped separately;

installation requirements depend on the size (see below).
Provide a minimum of 14" (356mm) clearance from the bottom of the air hood to the

mounting surface.

Hood and Filter Cabinet Options by ITEM and Application

Item

Options Description

For Sizes

Installation Requirements

1

AS2, AS6,

AS7

Outdoor Screened Air Hood

with & without filters

1-20, 1-40, 1-50,

1-65, 2-80, 2-120

Factory Assembled; Field Installed -

Follow instructions below.

2

AS2, AS6,

AS7

Outdoor Screened Air Hood

with & without filters

3-180, 3-260

Field Assembled and Installed - Follow

instructions pages 12 to 15.

3

AW3, AW6 Indoor Filter Cabinet with

Filters

All

Factory Assembled; Field Installed -

Follow instructions below.

CAUTION: It is

recommended

that the inlet to the

outside air hood

NOT be facing into

prevailing wind.

Installation STEPS for

ITEMS 1 and 3 in the

Table above - Refer to

FIGURE 10.

1) Remove the sheetmetal screws from the bottom rear inset and across the top rear

of the cabinet.

2) Align edges of assembly to the slip grooves. Slide top edge of assembly under the

lip formed by the top rear of the cabinet.

3) Rotate the inlet assembly so that it fits into the recess across the bottom of the

cabinet. Replace all screws removed in Step 1.

4) If the system has filters with an optional dirty filter light, follow the instructions

beginning on page 18 to attach the sensing tubes.

Advertising