0 electrical supply and wiring (cont'd) – Reznor RDF Unit Installation Manual User Manual

Page 18

Advertising
background image

I-RDF, PN148384R5, Page 18

Control Side

Control

Compartment*

Blower

Compartment

Supply Wiring**

24V Wiring**

Gas Supply

FIGURE 14 - Location of Gas

Connection, Electrical Supply

Connection, and Control Wiring

Connections on RDF Series 3

Direct-Fired Systems

NOTES:

* RDF-2 and RDF-3 Series 3 systems have double hinged

doors as illustrated. Control compartment on RDF-1 Series 3

systems has a single hinged door.

** Configuration shown is for RDF-2 and RDF-3 Series 3. The

supply connection on the RDF-1 Series 3 systems is above

the control wiring connection.

Disconnect

Switch

Location

FIGURE 15 - Remote

Console Dimensions

2-3/8

(60)

6 (152)

5-15/32 (139)

1-5/16 (33)

1-3/32 (28)

4-7/16

(113)

1-3/32 (28)

Locations of Knockout

Holes (dimensions to

centerlines)

Technical Data of the Remote Console (Variations depend on options selected; consult custom wiring diagram

for controls and to determine wiring required.)

Control

Switch

Qty of

Lights*

Temperature

Selector**

Potentiometer

***

Dimensions - inches (mm)

L****

H****

D

Yes

3

Yes

No

10-3/4 (273) 7-5/8 (194) 2-5/8 (67)

Yes

3

No

No

10-3/4 (273) 7-5/8 (194) 2-5/8 (67)

Yes

3

Yes

Yes

15-3/4 (400) 7-5/8 (194) 2-5/8 (67)

Yes

3

No

Yes

10-3/4 (273) 7-5/8 (194) 2-5/8 (67)

Yes

4

Yes

No

15-3/4 (400) 7-5/8 (194) 2-5/8 (67)

Yes

4

No

Yes

15-3/4 (400) 7-5/8 (194) 2-5/8 (67)

Yes

4

Yes

Yes

15-3/4 (400) 7-5/8 (194) 2-5/8 (67)

Yes

4

No

No

15-3/4 (400) 7-5/8 (194) 2-5/8 (67)

* 3 - Blower On, Burner On, and Safety Lockout on both RC13 and RC14; 4th light is

Dirty Filter Indicator on Option RC14 only

** On the console with Gas Control Options AG 31, 32, 33, 47, or 48

*** On the console with Air Control Options AR19 or AR22

**** Subtract 1" (25mm) when recessing

Dirty Filter Light

FIGURE 16 - Option

RC14 with Dirty

Filter Light and

Potentiometer

7.0 Electrical

Supply and

Wiring (cont'd)

Control Wiring (cont'd)

there is a brief description of the optional electrical controls used for airflow. Refer to

the operation manual, Form O-ADF/RDF, for additional control information.

Remote Console

If ordered, the optional remote console is shipped separately. Remote consoles include

terminal blocks for wiring. Depending on what gas control or inlet air options were

ordered, the console could include a temperature selector and/or a potentiometer. If

a dirty filter switch is ordered the indicator light is on the console. See

FIGURE 15 for

console size.

When a console with a dirty filter indicator is selected, the remote console includes a

fourth light (dirty filter indicator light). The light is activated by an adjustable, single-

pole/normally open differential pressure switch that senses air pressure across the

filter bank. There are field-installation procedures that must be done for the proper

operation of the dirty filter indicator light.

Dirty Filter Light Installation Instructions

Before the system is operating, connect the sensing tubes from the switch

to their sensing locations in the field-installed filter cabinet. (Cabinet installation

instructions are in Paragraph 6.2.)

1) Run the tubes through the holes in the cabinet wall. Pull gently to extend the

tubing to its entire length without stress.

2) Position the tubing approximately at the center of the height of the filter rack.

3) Identify the tube connected to the positive connection on the switch (

FIGURE

17) as the positive pressure tube. Determine the length of tubing required to

attach the

positive pressure tube so that it will sense pressure at the inlet

side of the filter rack.

Identify the tube connected to the negative connection on the switch (

FIGURE

17) as the negative pressure tube. Determine the length of tubing required to

Advertising