Supports, 4 mounting on a roof curb, 0 mounting (cont'd) – Reznor RDF Unit Installation Manual User Manual

Page 6: 3 mounting on field-supplied supports 5.1 weights, 2 rigging

Advertising
background image

I-RDF, PN148384R5, Page 6

5.3 Mounting on

Field-Supplied

Supports

5.1 Weights

NOTE: Net weights are approximate for the standard system. Optional equipment is

not included.

Net Weight of Basic Model RDF System

Sizes

1-20

1-40

1-50

1-65

2-80

2-120

3-180

3-260

lbs

915

925

935

950

1455

1505

2410

2480

kg

415

420

424

431

670

683

1093

1125

5.2 Rigging

All units are mounted on a full curb cap base furnished with four lifting lugs for attaching

rigging. To prevent damage to the cabinet, use spreader bars with the rigging chains.

FIGURE 2 - Placement of Mounting Rails

A

B

4 x 4 Treated Lumber

FIGURE 3 - Cross

Support Mounting

Requirements

Field

Supplied

Duct

Field

Supplied

Duct

4 x 4 Treated Lumber

= support location

Mounting Rail Placement

Model

A (inches) B (inches)

1-20, 1-40, 1-50, 1-65

85-1/4

45-1/2

2-80, 2-120

85-1/4

69-7/16

3-180, 3-260

132-5/8

83-1/16

Model

A (mm)

B (mm)

1-20, 1-40, 1-50, 1-65

2165

1156

2-80, 2-120

2165

1764

3-180, 3-260

3369

2110

5.4 Mounting on a

Roof Curb

CAUTION: Before installing curb, recheck to be sure that the

correct curb has been ordered. Be sure that the curb selected

matches the unit ordered. Verify the dimensions of the curb

received with the dimension table in FIGURE 4.

Roof Curb

Dimensions for Model

RDF Series 3

Whether the roof curb is Option CJ3 designed for the system or a field-supplied curb,

the roof curb dimensions in

FIGURE 4 and the ductwork opening dimensions in FIG-

URE 6 apply.

The roof curb designed for the system includes dividers that will create internal duct-

work and duct connection flanges for ease of installation and so that the building duc-

twork can be attached before the system is set on the roof curb.

The system is equipped with a load-bearing curb cap which forms an integral part of

the unit. The curb cap provides required clearance from combustibles. Whether the

system is being mounted directly on a surface or being placed "up" on additional struc-

ture, the horizontal length must be supported by two 4x4 treated wooden rails. Refer

to

FIGURE 2 for the appropriate lengths and spacing. When the system is placed on

the rails, the curb cap "skirt" must fit over the edge of the boards with the rails setting

inside the horizontal length of the curb cap.
If the rails are laid directly on the mounting surface, position them as shown in

FIGURE

3. Set the system on the rails leaving the "ends" underneath open for ventilation.

If the wooden rails are not placed directly on a surface, cross-supports should be

placed underneath the rails at the ends and at the cabinet "joint". Refer to

FIGURE 3.

IMPORTANT NOTE: Mount an outdoor unit with a minimum of 14" clearance from the

bottom of the inlet air hood to the mounting surface.

5.0 Mounting

(cont'd)

Advertising