I-RDF, PN148384R5, Page 21

Switching action in the pressure

null switch

Electric Box

Span

Adjust

Screw

Mounting Plate

Pressure Taps

Low

High

Pressure

Adjust

Screw

Increasing

Decreasing

Linkage to

Diaphragm

Low

Common

High

Span Adjustment

Span of

floating

contact

FIGURE 24 - Pressure

Null Switch included

in Air Control Options

AR20 and AR23

IMPORTANT: To eliminate shipping damage to the switch

contacts, the manufacturer reduced the span adjustment to zero

before shipping. The span should be adjusted prior to using the

switch. (If the switch has been installed, disconnect the vent

tube so that the null switch is in a neutral position.) Remove the

switch electrical box cover and while observing the contacts,

turn the span adjustment screw slowly in a clockwise direction.

Continue turning the adjustment screw until you are able to see

gaps between the common and both the low and high contacts.

A minimum gap provides the greatest sensitivity. The wider the

gap, the lower the sensitivity.

Optional Photohelic Pressure Switch (applies to systems with Air

Control Option AR36 for makeup air only or AR37 for outside and

recirculation air) -

If the system includes Air Control Option AR36, the discharge

damper is controlled by a photohelic pressure switch. If the system includes Air Control

Option AR37, the photohelic pressure switch controls the return air damper. The

photohelic pressure switch is shipped separately.

The photohelic switch uses relays to control between high and low pressure setpoints.

When the pressure changes, reaching either setpoint, the beam from an LED to the

limiting phototransistor will be cut off by the helix-driven light shield. The resulting sig-

nal change is electronically amplified to actuate its DPDT slave relay and switching

occurs. Pressure rating is 0" w.c. to .25" w.c.

Mount the switch with the scale vertical in a location where the ambient temperature is

between 20° and 120°F. Pneumatic pressure sensing lines may be run any distance.

Refer to the manufacturer's installation instructions and the wiring diagram to install

and connect this switch.

Optional Field-Provided Computer Control (applies to systems with

Air Control Option AR33 or AR34 and/or with Gas Control Option

AG37 or AG51 -

If the system includes Air Control Option AR33, the discharge

damper is controlled by a field-supplied 0-10VDC or 4-20 milliamp signal. If the

system includes Air Control Option AR34, the computer controls the return air damper.

With AG37, the gas valve and burner modulation are controlled by the field-supplied

computer signal. With AG51, the gas valve and burner modulation and outside air

damper are controlled by the field-supplied computer signal.
Follow the signal conditioner manufacturer's instructions included with the system for

connecting to the field-provided control.

FIGURE 25 -

Photohelic

Pressure Switch

FIGURE 26 - Signal

Conditioner

FIGURE 27 - Duct Smoke

Detector (cover removed)

Optional Photoelectric Duct Smoke

Detector -

If the system has an optional

photoelectric air duct smoke detector,

the control is shipped separately for field

installation. The sensor must be field-

mounted in the discharge duct and electrically

connected in the blower section electrical box.

Follow the manufacturer's instructions and the

wiring diagram for mounting and connecting the

control.