0 mechanical, 1 gas piping and pressures, Figure 7 - gas supply connection – Reznor RDF Unit Installation Manual User Manual

Page 9

Advertising
background image

I-RDF, PN148384R5, Page 9

6.1 Gas Piping and Pressures

All piping must be in accordance with the requirements of the National Fuel Gas Code

ANSI/Z223.1 (latest edition) or CSA B149.1 and B149.2. Gas supply piping installa-

tion must conform with good practice and with all local codes. Read this section of the

installation manual to determine the minimum gas supply pressure required to provide

a maximum gas capacity. Minimum gas supply pressure is also stated on the heater

rating plate. The heater manifold terminates at the gas supply connection with a black

iron pipe union. See

FIGURE 7. Local codes may require a 6" condensate trap. Gas

connection is either 1", 1-1/4", or 2" depending on the size of the system.

WARNING: High pressure testing of supply lines is acceptable, provided the supply

line has been disconnected from the unit and the pipe end is capped. See Hazard

Levels, page 2.

FIGURE 7 - Gas

Supply Connection

6.0 Mechanical

From Gas Supply

(horizontal or vertical)

Manual

shutoff

Drip

Leg

*To Gas

Valve

(inside the

cabinet)

*To Gas

Valve

(inside the

cabinet)

Ground

Joint

Union

Drip

Leg

Ground Joint Union

Manual shutoff

Capacity of Piping - Cubic Feet per Hour based on 0.3" w.c. Pressure Drop

Specific Gravity for Natural Gas -- 0.6 (Natural Gas -- 1000 BTU/Cubic Ft)

Specific Gravity for Propane Gas -- 1.6 (Propane Gas -- 2550 BTU/Cubic Ft)

Length

of Pipe

Diameter of Pipe

1"

1-1/4"

1-1/2"

2"

2-1/2"

3"

4"

Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane

20'

350

214

730

445

1100

671

2100

1281

3300

2013

5900

3599

12000

7320

30'

285

174

590

360

890

543

1650

1007

2700

1647

4700

2867

9700

5917

40'

245

149

500

305

760

464

1450

885

2300

1403

4100

2501

8300

5063

50'

215

131

440

268

670

409

1270

775

2000

1220

3600

2196

7400

4514

60'

195

119

400

244

610

372

1105

674

1850

1129

3250

1983

6800

4148

70'

180

110

370

226

560

342

1050

641

1700

1037

3000

1830

6200

3782

80'

170

104

350

214

530

323

990

604

1600

976

2800

1708

5800

3538

90'

160

98

320

195

490

299

930

567

1500

915

2600

1586

5400

3294

100'

150

92

305

186

460

281

870

531

1400

854

2500

1525

5100

3111

125'

130

79

275

168

410

250

780

476

1250

763

2200

1342

4500

2745

150'

120

73

250

153

380

232

710

433

1130

689

2000

1220

4100

2501

175'

110

67

225

137

350

214

650

397

1050

641

1850

1129

3800

2318

200'

100

61

210

128

320

195

610

372

980

598

1700

1037

3500

2135

Note: When sizing supply lines, consider possibilities of future expansion and increased requirements. Refer to National Fuel Gas Code for additional

information on line sizing.

Gas Supply Piping

Supply Pressure

Requirement by

Manifold Option

These direct-fired makeup air systems are designed to operate on a natural gas sup-

ply differential pressure range of a minimum of 4.3-5.0" w.c. plus the manifold pres-

sure drop. Maximum supply pressure depends on specific unit firing rate and manifold

selection. If the natural gas supply pressure is above the maximum allowed, it is nec-

essary to install a field-supplied step-down gas regulator in the supply line. Order and

install the appropriate Gas Regulator Kit, Option CZ1 (1") or CZ2 (1-1/2"). These kits

include spring-loaded, lockup type regulators that comply with national and local codes

specifying that type of regulator. Follow the instructions provided with the kit. Measure

the gas pressure between the step-down regulator and the unit.

WARNING: All components of the gas supply system must be leak tested prior to

placing equipment in service. NEVER TEST FOR LEAKS WITH AN OPEN FLAME.

Maximum Supply Pressure by Manifold

Manifold Option BM75, BM76, BM77 - 1/2 psi

Manifold Option BM78, BM79 - 2 psi

Manifold Option BM80, BM81 - 5 psi