0 mounting (cont'd), 4 mounting on a roof curb (cont'd), Roof curb installation instructions (cont'd) – Reznor RDF Unit Installation Manual User Manual

Page 8

Advertising
background image

I-RDF, PN148384R5, Page 8

Airflow

Assembled Dividers for Optional

Return Air Ductwork in the Roof Curb
Field-supplied ductwork may be either

“dropped in” from the top resting on

the top flange or be attached to the bottom

flange, using the dividers as ductwork.

Bottom

Discharge

Supply Air

Opening

(A x B)

Return

Air

Opening

(E x F)

A

C

B

D

E

F

G

H

3/4 (19)

3/4 (19)

Top View

FIGURE 6 - Divider Locations for

Bottom Ductwork Openings

NOTES:

• Drawing is not proportional for all sizes.
• 3/4" (19mm) measurement is the width of the

flanges where the roof curb mates with the

heater. Flange surface must be sealed.

• When cutting duct openings in the roof, cut

opening(s) 1” (25mm) larger than duct size

opening for installation clearance.

5.0 Mounting

(cont'd)

5.4 Mounting on a Roof Curb (cont'd)

Roof Curb Duct Opening Dimensions (± 1/8" or 3mm)

Sizes 1-20, 1-40, 1-50, 1-65

2-80, 2-120

3-180, 3-260

inches

mm

inches

mm

inches

mm

A

23-11/32

593

28-13/32

722

38

965

A

B

20-1/8

511

28-11/32

720

38

965

B

C

5

127

13-15/32

342

11-19/32

294

C

D

10-1/4

260

7

178

4-5/8

17

D

E

25-1/2

648

54-11/16

1389

66-3/4

1695

E

F

11-1/2

292

17-23/32

432

20-1/16

510

F

G

11-15/32

291

8

203

10-15/32

266

G

H

11-1/32

280

11-3/32

282

17-1/4

438

H

3. If the system has a bottom discharge and/or a return air inlet, use the sheetmetal

screws to sub-assemble the dividers. Refer to the dimensions in

FIGURE 6 to

appropriately position the roof curb dividers to create the needed duct opening

flanges. Attach the dividers to the roof curb with sheetmetal screws.

NOTE: If the

system does not have a bottom discharge and/or a return air opening, the dividers

for an opening that is not going to be used may be installed but are not required.

4. Check the assembly for squareness. The curb must be adjusted so that the

diagonal measurements are equal within a tolerance of ± 1/8".

5. Level the roof curb. To ensure a good weatherproof seal between the unit curb

cap and the roof curb, the roof curb must be leveled in both directions with no twist

end to end. Shim as required and secure curb to the roof deck before installing

flashing.

6. Install field-supplied flashing.
7. Before placing the RDF unit on the curb, apply furnished 1/4" x 1-1/4" foam sealant

tape to the top perimeter surface of the curb, making good butt joints at corners.

The sealant tape must be applied to the curb rails to prevent water leakage into

the curb area due to blown rain and capillary action.

Also place the foam sealant tape on the perimeter of the top surface of the duct

opening(s), being sure to make good butt joints at corners. If installing ductwork

from the top, it is recommended that tape be put on again after the ductwork is

"dropped in", sealing below and above the duct flanges.

Roof Curb Installation Instructions (cont'd)

Advertising